9-4. Installing the Drain Piping
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for the drain and
use the supplied drain socket to prevent water leaks.
The PVC pipe must be purchased separately.
When doing this, apply adhesive for the PVC pipe at the
connection point.
(2) If connecting a drain socket (supplied) to the threaded drain port,
first wrap the drain port threads with sealing tape, then connect
the joint. (Fig. 1-13)
(3) Ensure the drain pipe has a downward slant (1/100 or more).
(See the Fig. 1-14)
(4) The drain pipe with a trap should be installed away from the
indoor unit.
(5) Do not forcibly install the drain pipe to the indoor unit tubing.
If forcibly installed, it may result in water leakage.
(6) The drain pipe should be fixed at the nearest of the indoor unit.
Failure to do so may result in water leakage.
(7) Do not attach any air purge equipment.
If attached, drain water may result in splashing out of the drain
pipe.
(8) When the drain piping is completed, perform the water leak test
and check for a water leak.
If detected, it may result in water leakage or condensation.
(9) When the drain piping is completed, perform the drainage test
if the water drains smoothly.
If not draining smoothly, it may result in water leakage or
condensation.
(10) When the drain piping work is finished securely, wrap the
insulation material around the indoor side drain pipe.
At this time, do not wrap together with the refrigerant tubing.
If wraped together, the drain pipe is lifted and water drainage will
not be operated.
Coincidentally, the water comes out of the drain pan and it can
lead to water leakage.
*
a
*
b
Sealing tape
Drain pan
Downward slant
Min. 1/100
Inspection plug
*a: over 100mm
*b: over 50mm
Note:
Since the drain trap area easily accumulates
the dust inside the drain pipe, necessarily
install the plug in order to clean out the drain
trap.
Correct
Incorrect
Drain socket
(supplied)
Drain port
(25A male screw)
Fig. 1-13
Fig. 1-14
Fig. 1-15
9-5. Caution for Ducting Work
•
This unit has high static pressure.
In case of small pressure resistance (for instance, a short duct), install an airflow control damper (field supply)
for adjusting airflow volume as airflow volume / airflow noise increases.
•
If the air conditioner is to be installed in a room such as an office or meeting room which needs a low sound
level, provide a supply and return sound absorption chamber with an acoustic liner.
•
Use a flexible canvas connection or vibration isolation hanger (field supply) to break transmission of
mechanical vibration of the unit.
Sound absorbing chamber
Sound absorbing chamber
Air filter (field supply)
Inspection
opening
Ceiling panel
Indoor unit
Thermal
insulation
Thermal
insulation
Air-discharge
Air intake
Canvas connection
Sound absorbing chamber
Airflow control damper
Fig. 1-16
•
Use incombustible duct materials.
•
Use thermal insulation to prevent duct condensation.
•
An air filter (field supply) must be installed at the air intake side.
If not installed, the heat exchanger will get dirty and the unit will reduce the quality.
•
Obtain and install an air filter (field supply) which can easily wash away the dust by lukewarm, soapy
water orsuck up with a vacuum cleaner.
•
Clean the air filter periodically to collect dust and other particles from the air.
•
Use duct static pressure within a range of specification value.
CAUTION
SM830252-00_欧州_Single_天埋.indb 39
16/08/26 10:40:19
Содержание S-200PE2E5
Страница 70: ...1 64 MEMO SM830252 00_欧州_Single_天埋 indb 64 16 08 26 10 40 29 ...
Страница 86: ... MEMO 3 4 SM830252 00_欧州_Single_天埋 indb 4 16 08 08 13 11 45 ...
Страница 166: ... MEMO 7 16 SM830252 00_欧州_Single_天埋 indb 16 16 08 27 8 24 20 ...
Страница 188: ...201608 SM830252 00_欧州_Single_天埋 indb 1 16 08 10 15 45 43 ...