46
Table 10-2 Setting the external static pressure
Indoor unit type
Item code
15, 22, 28, 36,
45, 56, 60, 73
90, 106
112, 140,
160
B0
External static pressure of the rated
airflow volume (Pa)
150
150
150
0010
140
140
140
0009
130
130
130
0008
120
120
120
0007
110
110
110
0006
90
90
90
0005
70
70
70
0004
50
40 *
50 *
0003
30 *
30
30
0002
10
10
10
0001
No auto airflow volume setting
-001
Auto airflow volume setting
-002
* Airflow volume setting at shipment
NOTE:
Failure to set this parameter may result in decreased airflow and condensation.
6. Select the “Unit no.” by pressing the
or
button
and press the
button.
The “Exit detailed settings and restart?” (Detailed setting-
end) screen appears on the LCD display.
Select “YES” and press the
button.
When the setting is completed, perform the test run for the
external static pressure setting described in “Auto External
Static Pressure Setting Operation”.
Auto External Static Pressure Setting Operation
7. Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
8. Press the
or
button to see each menu.
If you wish to see the next screen instantly, press the
or
button.
Select “4. Test run” on the LCD display and press the
button.
The “Test run” screen appears on the LCD display.
Detailed settings
Unit no.
Code no.
Set data
ALL
Sel.
Next
20:30 (THU)
01
0002
Exit detailed settings
and restart?
NO
YES
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
Sel.
Page [
] Confirm
20:30 (THU)
4. Test run
[
] Confirm
Test run
Change
20:30 (THU)
Test run
OFF
01_350221_Eng.indb 46
2023/3/17 10:01:16