Tubing Data and Refrigerant
5
PAW-VP500LDHW
Combined with outdoor unit
Tubing data
U-100PZH2E8
Tubing size outer diameter
Liquid tube
[mm (in.)] 3/8”
Gas tube
[mm (in.)] 5/8”
Limit of tubing length (L)
[m] 30
Height differential of Indoor/
Outdoor units (H1)
Outdoor unit is placed higher
[m] 30
Outdoor unit is placed lower
[m] 15
Attention: follow instruction
Remove 1000 g for pipe length 7.5 m
Required additional refrigerant
[g/m] 45
Refrigerant charged at shipment R32
[kg] 3.05
PAW-VP200LDHW
Combined with outdoor unit
Tubing data
U-100PZH2E8
Tubing size outer diameter
Liquid tube
[mm (in.)] 3/8”
Gas tube
[mm (in.)] 5/8”
Limit of tubing length (L)
[m] 30
Height differential of Indoor/
Outdoor units (H1)
Outdoor unit is placed higher
[m] 30
Outdoor unit is placed lower
[m] 15
Attention: follow instruction
Remove 1400 g for pipe length 7.5 m
Required additional refrigerant
[g/m] 45
Refrigerant charged at shipment R32
[kg] 3.05
PAW-VP380L
Combined with outdoor unit
Tubing data
U-200PZH2E8
Tubing size outer diameter
Liquid tube
[mm (in.)] 3/8”
Gas tube
[mm (in.)] 1 1/8”
Limit of tubing length (L)
[m] 30
Height differential of Indoor/
Outdoor units (H1)
Outdoor unit is placed higher
[m] 30
Outdoor unit is placed lower
[m] 30
Systems must be pre-charged with refrigerant
[kg] 1
Required additional refrigerant over 7.5 meters
[g/m] 60
Refrigerant charged at shipment R32
[kg] 4.2
Содержание PAW-VP1000LDHW
Страница 2: ......
Страница 122: ...122 PAW VP LDHW Technical Manual 2019 11 Appendix A A 2 Spare parts Tanks ...
Страница 123: ...123 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 124: ...124 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 125: ...125 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 126: ...126 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 132: ......
Страница 133: ......
Страница 134: ...Polar Energi AS Postboks 117 9450 Hamnvik Norway www polarenergi com ...