39
PAW-VP•LDHW - Technical Manual – 2019-11
Important Peak Cut Settings
2
2.2 DHW set temperature
67°C
Set point 53°C
Δt 5.5
°
C
55°C
Set point
Low part tank
Middle part tank
Upper part tank
Mixing temperature
46
48 °C
50 °C
57 °C
52 °C
50
52 °C
54 °C
60 °C
56 °C
53
55 °C
57 °C
67 °C
61 °C
55
58 °C
60 °C
70 °C
63 °C
Maximum and Minimum frequency related to outdoor temperature
Heat pump (U-)
PZH
TO temp (Heating)
100PZH2
200PZH2
250PZH2
Hz +20/18
49
60
80
Hz +11/9
55
70
95
Hz +4/2
60
80
100
Hz -4/-20
65
95
110