PAW-VP•LDHW - Technical Manual – 2019-11
Tubing Data and Refrigerant
5
5 Tubing Data and Refrigerant
5.1 Tubing data for DHW and outdoor unit combination
PAW-VP1000LDHW
Combined with outdoor unit
Tubing data
U-250PZH2E8
Tubing size outer diameter
Liquid tube
[mm (in.)] 1/2”
Gas tube
[mm (in.)] 1 1/8”
Limit of tubing length (L)
[m] 30
Height differential of Indoor/
Outdoor units (H1)
Outdoor unit is placed higher
[m] 30
Outdoor unit is placed lower
[m] 30
Attention: follow instruction
Remove 600 g for pipe length 7.5 m
Required additional refrigerant over 7 meters
[g/m] 80
Refrigerant charged at shipment R32
[kg] 5.2
PAW-VP1000LDHW
Combined with outdoor unit
Tubing data
U-16MF3E8
Tubing size outer diameter
Liquid tube
[mm (in.)] 1/2”
Gas tube
[mm (in.)] 1 1/8”
Limit of tubing length (L)
[m] 50
Height Differential of
Indoor/Outdoor Units (H1)
Outdoor unit is placed higher
[m] 30
Outdoor unit is placed lower
[m] 30
Attention: follow instruction if piping under 15 m.
Over 50 m meters is not needed
Add receiver tank 3 liter
Required additional refrigerant over 7.5 meters
[g/m] 80
Refrigerant charged at shipment R410A
[kg] 8.3
The system must have extra refrigerant filling, please see installation manual for U-16MF3E8.
Содержание PAW-VP1000LDHW
Страница 2: ......
Страница 122: ...122 PAW VP LDHW Technical Manual 2019 11 Appendix A A 2 Spare parts Tanks ...
Страница 123: ...123 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 124: ...124 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 125: ...125 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 126: ...126 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 132: ......
Страница 133: ......
Страница 134: ...Polar Energi AS Postboks 117 9450 Hamnvik Norway www polarenergi com ...