104
PAW-VP•LDHW - Technical Manual – 2019-11
How to make Settings
9
9.2 Detailed settings for indoor/outdoor unit RTC5B/RTC2/4
The new value must be set during the commissioning
U-100PZH2E5/VP200LDHW
Tank controller CZ-RTC5B detailed settings
Explanation
Check and adjust
Parameter
Default value
New value to set
10
0031
0031
Water unit
11
0012
0012
Indoor capacity type 100
16
0015
0000
No fan
2C
0000
0006
No expansion valve
Outdoor unit detailed settings by RTC2/4
Explanation
Check and adjust
Parameter
Default value
New value to set
20
-015
-035
Th. Off differential change from 1.5 k to 3.5 k
21
150
600
Th. Off judging time in sec.
4E
000
+005
Condensing temperature lower limit
4F
000
+005
Condensing temperature upper limit
42
-002
000
Condensing temp. offset from -2 k to 0 k
A5
000
030
Frost adherence temp. change from -2 °C to -4 °C
U-100PZH2E5/VP500LDHW
Tank controller CZ-RTC5B detailed settings
Explanation
Check and adjust
Parameter
Default value
New value to set
10
0031
0031
Water unit
11
0012
0015
Indoor capacity type 100
16
0015
0000
No fan
2C
0000
0006
No expansion valve
Outdoor unit detailed settings by RTC2/4
Explanation
Check and adjust
Parameter
Default value
New value to set
20
-015
-035
Th. Off differential change from 1.5 k to 3.5 k
21
10
600
Th. Off judging time in sec.
4E
000
+005
Condensing temperature lower limit
4F
000
+005
Condensing temperature upper limit
42
-002
000
Condensing temp. offset from -2 k to 0 k
A5
000
030
Frost adherence temp. change from -2 °C to -4 °C
U-250PZH2E8/PAW-VP750LDHW
Tank controller CZ-RTC5B detailed settings
Explanation
Check and adjust
Parameter
Default value
New value to set
10
0031
0031
Water unit
11
0012
0023
Indoor capacity type 250
16
0015
0000
No fan
2C
0000
0006
No expansion valve
Outdoor unit detailed settings by RTC2/4
Explanation
Check and adjust
Parameter
Default value
New value to set
20
-015
-035
Th. Off differential change from 1.5 k to 3.5 k
21
180
600
Th. Off judging time in sec.
4E
000
+005
Condensing temperature lower limit
4F
000
+005
Condensing temperature upper limit
42
-002
000
Condensing temp. offset from -2 k to 0 k
A5
000
030
Frost adherence temp. change from -2 °C to -4 °C
Содержание PAW-VP1000LDHW
Страница 2: ......
Страница 122: ...122 PAW VP LDHW Technical Manual 2019 11 Appendix A A 2 Spare parts Tanks ...
Страница 123: ...123 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 124: ...124 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 125: ...125 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 126: ...126 PAW VP LDHW Technical Manual 2019 11 Appendix A ...
Страница 132: ......
Страница 133: ......
Страница 134: ...Polar Energi AS Postboks 117 9450 Hamnvik Norway www polarenergi com ...