3.3.3 Aquarea basic configuration
(only needed for connection via Bus)
The HPM controller serves as a substitute for the Aquarea operating unit. Therefore,
all parameter adjustments needed for initial installation of the heat pump must be
performed via the menu structure of the HPM. This includes necessary basic
configuration and parameters as these are described in the operating and service
manuals of the Panasonic heat pump(s).
To do this, press “OK” in the default menu and open the “MCR/BMS” menu. Select
the item “
heat producer
” using “DOWN” and enter the menu using “OK”.
Depending on the system diagram loaded (one or more heat pumps) the menu
structure of the heat pump module will either be automatically displayed, or it will be
necessary to select heat pump 1-3 by using “UP”, “DOWN” and “OK”.
x
In the menu for the heat pump, select the menu “
function
” using “DOWN” and
“OK”.
x
In the “
function
” menu, select the menu item “
Aquarea
” using “DOWN” and
“OK”.
x
In the “
Aquarea
” menu, select the menu “
settings
” using “DOWN” and “OK”.
This menu contains the most important parameters, displayed in the table below with
their default values. Some of the parameters will already have been automatically
adjusted when the system diagram was selected (e.g. DHW tank included or not):
Name
Info text
Range / default value
Thermos
Room thermostat
0:no, 1:yes
Tank
Tank Connection
0:no, 1:yes
SolarPrio
Solar Priority
0:no, 1:yes
HeatPrio
Heating Priority
0:no, 1:yes
Steril.
Sterilization
0:no, 1:yes
basPanH
bas pan heater
0:no, 1:yes
CoolPrio
Cooling Priority
0:no, 1:yes
AntiFr
Antifreezing
0:no, 1:yes
OpInt
Operation Interval
range: 30-600 min, default: 180 min
TankInt
Tank heat Interval
range: 5-95 min, default: 30 min
BoostDel
Booster Delay
range: 20-95 min, default: 60 min
SterTemp
Sterilisation boiling temperature
range: 40-75 °C, default: 70 °C
SterTime
Sterilization continuing time
range: 5-60 min, default: 10 min
HeaterC
Heater Capacity
range: 0, 3, 6 ,9 KW, default: 0 kW
OutTOn
Outdoor temp heater on
range: -15-20 °C, default: 0 °C
Table 3.4: Aquarea setting parameters
After adjusting the parameters, the power supply for the heat pump must be switched
off in order to connect the adapter cable PAW-HPINT-x to the main PCB inside the
heat pump (instead of the cable coming from the operating unit) The other side of the
adapter cable must be connected to the BUS interface of the HPM controller. The heat
pump will emit a beep if the connection was successful.
3.3.4 Domestic hot water – Setpoints
If setpoints differing from the basic values (45°C) should exist for the domestic hot
water tank, these can be adjusted. Different values for occupation times 1…4 can be
selected, as well as non-occupation time and special non-occupation time (holiday).