30
3.2.2 Reloading the system diagram
The system diagram can be reloaded at any time, e.g. if the automatic configuration
was incomplete due to a power failure or if you want to select a different system
diagram. The following steps must then be performed:
1.
Press and hold “OK” until the controller asks for an access code. Using “+”,
“-“ and “OK”, enter the access code “4444”.
2.
Press “OK” and the controller will switch to the “MCR/BMS” menu.
Pressing “UP” will navigate to the main menu.
3.
Using “DOWN”, select the “System diagram“ menu item. Press “OK” to
enter the “System diagram” menu.
4.
Change the parameter
sysDiagram
to your selected system diagram number
by using “+”, “-“ and “OK”.
5.
Press “DOWN“ to select the parameter
type sensor
. Changing the default
setting (“0”) is only necessary if a foreign sensor (1=Ni1000, 2=NI1000LG)
will be used. Choose the desired sensor type for the system by using “+”, “-“
and “OK”.
6.
When selecting a system diagram which includes communication with the
heat pump(s) (4xxxx; 5xxxx, 6xxxx, 7xxxx), the type(s) of heat pumps must
be entered in the parameters
type-HP1
,
type-HP2
and
type-HP3
. Here, the
identification “-1” (according to the type label on the heat pump) must be
entered (e.g. “SXC12D90E8-1”). “+”, “-“ and “OK” enables adjusting each
character in the line.
7.
If the type entered is not accepted when pressing “OK”, then communication
with a heat pump of this type is not possible. An overview of all compatible
heat pumps is contained in the appendix.
8.
Use “DOWN” to select the parameter
cold start
. Change the parameter
to”1” by using “+”. Press “OK”.
9.
When the display shows “SYSTEM XXXXX LOADED”, the process is
complete. The controller is now ready for operation.
CAUTION!
When performing a cold start, all previously performed
adjustments are lost and all parameters are reset to their
default values!
3.2.3 Manual configuration (loading of diagram “99999”)
If the HPM tool is not offering a system diagram number that fits the current system,
the system diagram “99999” can be selected and the entire controller then configured
manually.
After setting the type of heat pump to “1= release via contact” or to the actual product
type (e.g. “SXC12D90E8-1”) or to “” ” (no type) = HP not existing“, the selection for
the other control circuits (buffer tank, DHW circuit and heating circuits) should also
be set to a value (0,1,2). When performing a cold start, the controller will be freshly
initialized.
After the cold start, all input and output terminals of the control circuits must be
assigned according to the system specifications.