43
Installation
4.2 Installation of refrigerant piping
When installing the refrigerant piping, the following limitations and restrictions need to be
observed:
●
Maximum actual and equivalent piping length
● Maximum branch pipe length to AHU Kit
● Maximum branch pipe length diff erence (between longest and shortest piping from
the fi rst branch)
●
Dimensions of connecting pipes to heat exchanger of AHU system
●
Precharged pipe length of outdoor unit
●
Additional refrigerant charging amount for longer pipe runs
●
Other technical data and limitations of the relevant outdoor units
● Local piping design regulations
●
Best practices for piping design
● Instructions for the safe handling of R32 (see
→
1.4 Instructions for safe handling
of R32)
Important
For technical data, limitations and restrictions not mentioned in this document, refer to the tech-
nical documentation for the relevant ECOi, ECO G and PACi outdoor units.
4.3 Installation of expansion valve
Installation of expansion valve – ECOi and ECO G systems
NOTICE
Damage to the expansion valve wires
Exposing the wires of the expansion valve to the outside and/or to direct sunlight might damage
the wires and should therefore be avoided.
► Attach the AHU Kit either directly to the Air Handling Unit or to a wall nearby and make
sure that it is not exposed to direct sunlight.
►
Use protecting wire ducts to avoid exposing the wires of thermistors and the electronic
expansion valve to the outside.