Product description
Additional contacts available
● External humidifi er control (ON/OFF) 230 V AC 3 A
»
Terminal HU1; HU2.
● External fan control (ON/OFF) 12 V DC
»
Terminal FD1; FD2.
● External fi lter status signal potential free
»
Terminal FI1; FI2.
● External fl oat switch signal potential free
»
Terminal FS1; FS2.
● External leakage detection sensor or TH. OFF contact potential free (possible usa-
ge for external blow out temperature control)
»
Terminal EX1; EX2
Mounting boards
1
2
3
4
Upper mounting board – front side
1 Remote controller (CZ-RTC2 / CZ-RTC4)
2 Thermostat (TR-16 / TR-16e)
1
3 External signal control PCB (PAW-T10)
1
4 Terminal board with 6 connectors (labelled
Section A to Section F) each with 20 con-
tacts
2
8
9
5
6
7
Upper mounting board – rear side
5 Pocket for thermostat
6 CZ-CAPBC2 interface for 0-10 V control
(PCB name: ACC-SP1A)
1
7 Main control board
(PCB name: CR-UXRP71B-P)
8 Terminal for upper mounting board
9 EMC fi lter
1