33
Product description
Technical data and limitations – ECOi and ECO G systems –
R410A
AHU Kit HP
5
10
20
30¹
40¹
AHU Kit model
PAW-160MAH2(L/M)
PAW-280MAH2(L/M)
PAW-560MAH2(L/M)
PAW-280MAH2(L/M) +
PAW-560MAH2(L/M)
PAW-560MAH2(L/M) +
PAW-560MAH2(L/M)
Nominal cooling capacity
kW
14.0
28.0
56.0
84.0
112.0
Nominal heating capacity
kW
16.0
31.5
63.0
95.0
127.0
Air volume fl ow (Cooling)
Min
m³/h
1,140
3,500
7,000
10,500
14,000
Max
m³/h
2,600
5,000
10,000
15,000
20,000
AHU DX coil heat exchanger volume Min
dm
3
1.7
2.8
5.6
8.4
11.2
Max
dm
3
2.8
5.4
10.7
16.1
21.4
Bypass factor
0.9 (recommended) 0.9 (recommended) 0.9 (recommended) 0.9 (recommended) 0.9 (recommended)
Piping length
Min / Max
m
10 / 100
10 / 100
10 / 100
10 / 100
10 / 100
Max. branch pipe length
m
12
12
12
12
12
Max. branch pipe length difference after fi rst branch
m
10
10
10
10
10
Elevation difference (in/out)
Max
m
10
10
10
10
10
Piping connections
Liquid pipe
Inch (mm) 3/8 (9.52)
3/8 (9.52)
5/8 (15.88)
3/4 (19.05)
3/4 (19.05)
Gas pipe
Inch (mm) 5/8 (15.88)
7/8 (22.22)
1 1/8 (28.58)
1 1/4 (31.75)
1 1/2 (38.15)
Intake temperature of AHU Kit
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
°C WB
13 / 23
13 / 23
13 / 23
13 / 23
13 / 23
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
Ambient temperature (outdoor unit)
Cooling (Min / Max) °C DB
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
Heating (Min / Max) °C WB
-20 / 15
-20 / 15
-20 / 15
-20 / 15
-20 / 15
AHU Kit HP
50¹
60¹
70¹
80¹
AHU Kit model
PAW-560MAH2(L/M) +
PAW-560MAH2(L/M) +
PAW-280MAH2(L/M)
PAW-560MAH2(L/M) +
PAW-560MAH2(L/M) +
PAW-560MAH2(L/M)
PAW-560MAH2(L/M) +
PAW-560MAH2(L/M) +
PAW-560MAH2(L/M) +
PAW-280MAH2(L/M)
PAW-560MAH2(L/M) +
PAW-560MAH2(L/M) +
PAW-560MAH2(L/M) +
PAW-560MAH2(L/M)
Nominal cooling capacity
kW
140.0
168.0
196.0
224.0
Nominal heating capacity
kW
155.0
189.0
219.0
252.0
Air volume fl ow (Cooling)
Min
m³/h
17,500
21,000
24,000
28,000
Max
m³/h
25,000
30,000
35,000
40,000
AHU DX coil heat exchanger volume Min
dm
3
14.0
16.8
19.6
22.4
Max
dm
3
26.8
32.1
37.5
42.8
Bypass factor
0.9 (recommended) 0.9 (recommended) 0.9 (recommended) 0.9 (recommended)
Piping length
Min / Max
m
10 / 100
10 / 100
10 / 100
10 / 100
Max. branch pipe length
m
12
12
12
12
Maxi.branch pipe length difference after fi rst branch
m
10
10
10
10
Elevation difference (in/out)
Max
m
10
10
10
10
Piping connections
Liquid pipe
Inch (mm) 3/4 (19.05)
3/4 (19.05)
7/8 (22.22)
7/8 (22.22)
Gas pipe
Inch (mm) 1 1/2 (38.15)
1 1/2 (38.15)
1 5/8 (41.28)
1 3/4 (44.45)
Intake temperature of AHU Kit
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 32
18 / 32
°C WB
13 / 23
13 / 23
13 / 23
13 / 23
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
Ambient temperature (outdoor unit)
Cooling (Min / Max) °C DB
-10 / 43
-10 / 43
-10 / 43
-10 / 43
Heating (Min / Max) °C WB
-20 / 15
-20 / 15
-20 / 15
-20 / 15
1
Not applicable for ECO G systems.