Product description
Technical data and limitations – PACi systems –
R32
AHU Kit
PAW-280PAH2(L/M)
Outdoor unit – PACi Standard
U-60PZ2E5 U-71PZ2E5 U-100PZ2E5 U-125PZ2E5 U-140PZ2E5 U-100PZ2E8 U-125PZ2E8 U-140PZ2E8
Nominal cooling capacity
kW
6.0
7.1
10.0
12.5
14.0
10.0
12.5
14.0
Nominal heating capacity
kW
6.0
7.1
10.0
12.5
14.0
10.0
12.5
14.0
Piping connections
Liquid pipe
Inch (mm) 3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
Gas pipe
Inch (mm) 5/8" (15,88) 5/8" (15,88) 5/8" (15,88) 5/8" (15,88) 5/8" (15,88) 5/8" (15,88) 5/8" (15,88) 5/8" (15,88)
Ambient temperature
Cooling (Min / Max) °C DB
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
-10 / 43
Heating (Min / Max) °C WB
-15 / 24
-15 / 24
-15 / 24
-15 / 24
-15 / 24
-15 / 24
-15 / 24
-15 / 24
AHU unit under “standard conditions”
Air volume fl ow
Cooling (Min / Max) m³/h
780 / 1,320
780 / 1,320
900 / 2,160
1,140 / 2,280 1,200 / 2,400 900 / 2,160
1,140 / 2,280 1,200 / 2,400
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU DX coil heat exchanger volume Min / Max
dm
3
1.3 / 1.4
1.3 / 1.4
1.5 / 1.9
1.5 / 1.9
1.5 / 1.9
1.5 / 1.9
1.5 / 1.9
1.5 / 1.9
Heat exchanger face area
Min / Max
m
2
– / –
– / –
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
Piping length
Min / Max
m
3 / 40
3 / 40
5 / 50
5 / 50
5 / 50
5 / 50
5 / 50
5 / 50
Precharged length (
R32
)
Max
m
30
30
30
30
30
30
30
30
Additional refrigerant charge (
R32
) due to extended piping
length
g/m
35
35
45
45
45
45
45
45
AHU unit under “special conditions A
2
”
Air volume fl ow,
subject to restrictions
2
Cooling (Min / Max) m³/h
780 / 1,450
780 / 1,600
900 / 2,300
1,140 / 2,500 1,200 / 2,600 900 / 2,300
1,140 / 2,500 1,200 / 2,600
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU unit under “special conditions B
3
”
AHU DX coil heat exchanger volume,
subject to restrictions
3
Min / Max
dm
3
1.3 / 1.8
1.3 / 2.0
1.5 / 2.6
1.5 / 2.6
1.5 / 2.8
1.5 / 2.6
1.5 / 2.6
1.5 / 2.8
Additional refrigerant charge (
R32
) due to larger heat
exchanger volume
kg/dm
3
0.83
0.83
0.83
0.83
0.83
0.83
0.83
0.83
Max. additional refrigerant charge (
R32
)
kg
0.33
0.50
0.58
0.58
0.74
0.58
0.58
0.74
Max. pipe length
m
30
25
35
35
35
35
35
35
Max. ambient temp. for pump down
°C
n/a
n/a
35
25
35
35
25
35
AHU Kit
PAW-280PAH2(L/M)
Outdoor unit – PACi Elite
U-36PZH2E5
U-50PZH2E5
U-60PZH2E5
U-71PZH2E5
U-100PZH2E5 U-125PZH2E5 U-140PZH2E5
Nominal cooling capacity
kW
3.6
5.0
6.0
7.1
10.0
12.5
14.0
Nominal heating capacity
kW
4.0
5.6
7.0
8.0
11.2
14.0
16.0
Piping connections
Liquid pipe
Inch (mm) 1/4” (6,35)
1/4” (6,35)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
Gas pipe
Inch (mm) 1/2” (12,7)
1/2” (12,7)
5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
Ambient temperature
Cooling (Min / Max) °C DB
-15 / 46
-15 / 46
-15 / 46
-15 / 46
-15 / 46
-15 / 46
-15 / 46
Heating (Min / Max) °C WB
-20 / 18
-20 / 18
-20 / 18
-20 / 18
-20 / 18
-20 / 18
-20 / 18
AHU unit under “standard conditions”
Air volume fl ow
Cooling (Min / Max) m³/h
360 / 870
510 / 990
780 / 1,320
780 / 1,320
900 / 2,160
1,140 / 2,280
1,200 / 2,400
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU DX coil heat exchanger volume Min / Max
dm
3
– / 1.3
– / 1.3
– / 1.4
– / 1.8
1.7 / 2.1
1.7 / 2.1
1.7 / 2.1
Heat exchanger face area
Min / Max
m
2
– / –
– / –
– / –
– / –
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
Piping length
Min / Max
m
3 / 40
3 / 40
3 / 40
5 / 50
5 / 85
5 / 85
5 / 85
Precharged length (
R32
)
Max
m
30
30
30
30
30
30
30
Additional refrigerant charge (
R32
) due to larger heat
exchanger volume
g/m
20
20
35
45
45
45
45
AHU unit under “special conditions A
2
”
Air volume fl ow,
subject to restrictions
2
Cooling (Min / Max) m³/h
360 / 870
510 / 1,080
780 / 1,600
780 / 1,700
900 / 2,400
1,140 / 2,600
1,200 / 2,700
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU unit under “special conditions B
3
”
AHU DX coil heat exchanger volume,
subject to restrictions
3
Min / Max
dm
3
– / 1.5
– / 1.5
– / 1.9
– / 2.2
1.7 / 3.0
1.7 / 3.0
1.7 / 3.0
Additional refrigerant charge (
R32
) due to larger heat
exchanger volume
kg/dm
3
0.83
0.83
0.83
0.83
0.83
0.83
0.83
Max. additional refrigerant charge (
R32
)
kg
0.17
0.17
0.41
0.33
0,74
0,74
0,74
Max. pipe length
m
30
30
30
40
65
65
65
Max. ambient temp. for pump down
°C
n/a
n/a
n/a
35
43
43
43
To be continued on next page. See footnotes overleaf.
21.05.2019, CH
Folgende Angaben hatte ich für die erste
Version (14-003-103-EU) dem alten, von
Panasonic erstellten DX+PACi-Handbuch
für R410A übernommen. Aber wo kriege
ich diese Angaben für R32 her? oder sind sie
identisch?
- AHU DX coil heat exchanger volume
- Heat exchanger face area
Außerdem ist folgende Angabe nicht in Jonas‘
Excel-Datei vorhanden:
- Max. ambient temp. for pump down
09.07.2019, CH:
Alle Angben von Jonas erhalten.
Содержание PAW-160MAH2
Страница 3: ...Air Handling Unit Kit Installation Instructions SET AL1 OUT ATU PV SV ºC ºC ...
Страница 4: ......
Страница 99: ...97 ...
Страница 100: ...Notes ...
Страница 101: ...Notes ...