14
General information and safety instructions
U-200PZH2E8, U-250PZH2E8
6.5 7.0 7.5 8.0 8.5
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
1.22
7.80
0.5
0.0
[m
c
]: refrigerant charge (kg) of the outdoor unit
Can be installed
Can not be installed
45.0
20.0
25.0
30.0
35.0
40.0
15.0
10.0
5.0
0.0
[A
min
]: minimum indoor floor area (m
2
)
Elite
U-200PZH2E8
U-250PZH2E8
[m
max
] (kg)
7.80
1.4.2 Preventing leakages
● Do not let air enter the refrigeration cycle, because this will increase the risk of
explosion and injury due to high tension inside the refrigerant cycle.
● Keep all tubing runs as short as possible.
● Use the fl are method for connecting tubing and apply refrigerant lubricant to the
matching surfaces of the fl are and union tubes before connecting them, then tigh-
ten the nut with a torque wrench for a leak-free connection.
● Do not leak refrigerant while working on the refrigerant tubes during installation,
maintenance or repair.
● Check carefully for leaks (see → 1.4.3 Detecting leaks) before starting the test run.