FP2 Analog Unit
Analog I/O Conversion Characteristics and Conversion Cycle Time
6 - 4
6.1
Analog Input Conversion Characteristics
-100mV to +100mV DC
(K)
(mV)
+32767
+16383
0
+50
+100
-50
-100
-16384
-32768
Input range -100mV to +100mV DC
V
K
-100
-32768
-75
-24576
-50
-16384
-25
-8192
0
0
25
8191
50
16383
75
24574
100
32767
If the input value exceeds the rated analog input range, the converted value becomes:
Input value
Converted value
-100mV or less
-32768
+100mV or more
+32767