FP2 Analog Unit
Troubleshooting
13 - 4
13.2 Problems Concerning the Analog Output
13.2 Problems Concerning the Analog Output
Problem
Remedy
Proper analog output cannot be
obtained.
Make sure that the FP2 CPU unit is in RUN mode.
Check the I/O allocation for the analog units.
Check the range settings.
Check the settings for no execution of conversion processing (shared
memory setting).
Make sure that the analog output data given to the analog unit is proper
for the range.
For current output, make sure that the impedance of the output load
device is 300
Ω
or less.
Check the analog signal wiring.
Analog output value is unsteady.
Make sure that you are using shielded twisted-pair wiring for the output
signal wires.
Make sure that the shielding of the shielded twisted-pair wiring is proper-
ly connected.
Make sure that no output signal wires are near other power wires.
Check the sequence program that gives the output data to the analog
unit.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание FP2 -C1A
Страница 23: ...Chapter 3 Wiring Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 24: ...FP2 Analog Unit Wiring 3 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 37: ...Chapter 5 Initial Settings Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 99: ...Chapter 13 Troubleshooting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 100: ...FP2 Analog Unit Troubleshooting 13 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 103: ...Chapter 14 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 104: ...FP2 Analog Unit Specifications 14 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...