FP2 Analog Unit
Specifications
14 - 16
14.4 Shared Memory for Analog Input Processing
14.4.5
Offset Changing Setting (address 30 to 37)
Sets the offset data for each channel that executes offset changing (range: -2048 to
+2047).
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Address 30
to
Address 37
K-2048 to K2047
(Default: K0)
Bit position
Address 30: Analog input ch 0
Address 31: Analog input ch 1
Address 32: Analog input ch 2
Address 33: Analog input ch 3
Address 34: Analog input ch 4
Address 35: Analog input ch 5
Address 36: Analog input ch 6
Address 37: Analog input ch 7
14.4.6
Input Sensor (TC, R.T.D.) Broken Wire Detection Flag (address 42)
Detects broken wires in the input wiring onlly for each input channel tha is set for the
thermocouple input range or R.T.D. (resistance thermometer device) input range, and
copies the data to the bits shown below.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Address 42
0: Normal
1: Broken wire detected
ch 7 ch 6 ch 5 ch 4 ch 3 ch 2 ch 1 ch 0
Bit position
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание FP2 -C1A
Страница 23: ...Chapter 3 Wiring Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 24: ...FP2 Analog Unit Wiring 3 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 37: ...Chapter 5 Initial Settings Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 99: ...Chapter 13 Troubleshooting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 100: ...FP2 Analog Unit Troubleshooting 13 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 103: ...Chapter 14 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 104: ...FP2 Analog Unit Specifications 14 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...