FP2 Analog Unit
Initial Settings
5 - 4
5.1
Analog Input Initial Settings
5.1.2
Analog Input Range Setting
Specifies the input range code when setting input ranges for each input channel.
(Set the range setting switch to ”Enable setting by software” and conversion will not be
executed for that input channel if there is not input range code specification.)
Program example:
When ch0:
±
10V, ch1: 1 to 5V, ch2: thermocouple K, and ch3: R.T.D. Pt100
R9013
F151 WRT , K0 , DT 0 , K2 , K18
Shared memory address 18 is head address
DT0 = H0701
DT1 = H120E
When the analog input
unit is installed at slot 0
Initial setting
5.1.3
Average Processing Times Setting
Specifies the average times for each input channel.
If there is no specification for the average times, then that input channel will perform
normal sampling.
Also:
K0 (0 times) is specified: No average processing, and normal sampling processing.
K1 (1 time) is specified: No average processing, and normal sampling processing.
K2 (2 times) is specified: No average processing, and normal sampling processing.
Other than K0 to K64 (0 to 64 times) is specified: average processing is performed with
K64 as the specified setting.
Program example:
When ch0: No average processing, ch1: 3 times, ch2: 10 times, ch3: 20 times
R9013
F151 WRT , K0 , DT0 , K4 , K22
Shared memory address 22 is head address
DT0 = K0
DT1 = K3
DT2 = K10
DT3 = K20
When the analog input
unit is installed at slot 0
Initial setting
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание FP2 -C1A
Страница 23: ...Chapter 3 Wiring Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 24: ...FP2 Analog Unit Wiring 3 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 37: ...Chapter 5 Initial Settings Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 99: ...Chapter 13 Troubleshooting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 100: ...FP2 Analog Unit Troubleshooting 13 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 103: ...Chapter 14 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 104: ...FP2 Analog Unit Specifications 14 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...