I/O Allocation
FP0
5
−
5
5.3
Expansion I/O Unit
5.3
Expansion I/O Unit
Up to three expansion I/O units can be added.
I/O numbers do not need to be set as I/O
allocation is performed automatically by
the FP0 control unit when an expansion
I/O unit is added.
The I/O allocation of expansion I/O unit
is determined by the installation location.
I/O number
Type
First expansion
Second
expansion
Third expansion
E8RS/E8RM
Input: 4 points
X20 to X23
X40 to X43
X60 to X63
/
Output: 4 points
Y20 to Y23
Y40 to Y43
Y60 to Y63
E8X
Input: 8 points
X20 to X27
X40 to X47
X60 to X67
E8YT/E8YP
Output: 8 points
Y20 to Y27
Y40 to Y47
Y60 to Y67
E16RS/E16RM/
E16T/E16P
Input: 8 points
X20 to X27
X40 to X47
X60 to X67
/
/
E16T/E16P
Output: 8 points
Y20 to Y27
Y40 to Y47
Y60 to Y67
E16X
Input: 16 points
X20 to X2F
X40 to X4F
X60 to X6F
E16YT/E16YP
Output: 16 points
Y20 to Y2F
Y40 to Y4F
Y60 to Y6F
E32T/E32P
Input: 16 points
X20 to X2F
X40 to X4F
X60 to X6F
/
Output: 16 points
Y20 to Y2F
Y40 to Y4F
Y60 to Y6F
A21
Input channel 0: 16
points
WX2
(X20 to X2F)
WX4
(X40 to X4F)
WX6
(X60 to X6F)
Input channel 1: 16
points
WX3
(X30 to X3F)
WX5
(X50 to X5F)
WX7
(X70 to X7F)
Output: 16 points
WY2 (Y20 to Y2F)
WY4 (Y40 to Y4F)
WY6 (Y60 to Y6F)
A80,
TC4,
TC8
Input CH0, 2, 4, 6: 16
points
WX2
(X20 to X2F)
WX4
(X40 to X4F)
WX6
(X60 to X6F)
C ,
TC8
Input CH1, 3, 5, 7: 16
points
WX3
(X30 to X3F)
WX5
(X50 to X5F)
WX7
(X70 to X7F)
A04V, A04I
Input: 16 points
WX2 (X20 to X2F)
WX4 (X40 to X4F)
WX6 (X60 to X6F)
,
Output CH0, 2, 4, 6: 16
points
WY2
(Y20 to Y2F)
WY4
(Y40 to Y4F)
WY6
(Y60 to Y6F)
Output CH1, 3, 5, 7: 16
points
WY3
(Y30 to Y3F)
WY5
(Y50 to Y5F)
WY7
(Y70 to Y7F)
IOL
Input: 32 points
X20 to X3F
X40 to X5F
X60 to X7F
Output: 32 points
Y20 to Y3F
Y40 to Y5F
Y60 to Y7F
−
The channel data of FP0
−
A80, TC4, TC8, A04V and A04I will switch and be read or
written by a user program that contains the conversion data switch flag.
−
Please verify with the manual for the FP0 CC
−
Link Slave unit.
Third expansion
Second expansion
First expansion
Control unit
Содержание FP0 Series
Страница 14: ...Table of Contents FP0 xii ...
Страница 16: ...Overview FP0 1 2 ...
Страница 82: ...S LINK Control Unit FP0 4 2 ...
Страница 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Страница 96: ...I O Allocation FP0 5 2 ...
Страница 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Страница 102: ...Installation FP0 6 2 ...
Страница 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Страница 114: ...Wiring FP0 7 2 ...
Страница 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Страница 200: ...General use Serial Communications FP0 10 2 ...
Страница 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Страница 220: ...Specifications FP0 12 2 ...
Страница 234: ...Dimensions FP0 13 2 ...
Страница 241: ...Dimensions FP0 13 9 13 6 Detailed Specifications of Cables 13 6 Detailed Specifications of Cables ...
Страница 243: ...Chapter 14 Appendix ...
Страница 380: ...14 138 14 7 ASCII Codes ...