14-88
Num-
ber
Name Boolean
Operand
Description
Steps
F142
P142
Watching
dog timer
update
WDT
PWDT
S
The time (allowable scan time for the system) of
watching dog timer is changed to “S”
×
0.1 (ms) for
that scan.
3
F143
P143
Partial I/O
update
IORF
PIORF
D1, D2
Updates the I/O from the number specified by “D1”
to the number specified by “D2”.
5
F144
Serial data
communica-
tion control
TRNS
S, n
The COM port received flag (R9038) is set to off to
enable reception.
Beginning at “S”, “n” bytes of the data registers are
sent from the COM port.
5
F145
P145
Data send
SEND
PSEND
S1, S2, D, N
Sends the data to another station in the network
(MEWNET).
9
F146
P146
Data receive
RECV
PRECV
S1, S2, N, D
Receives the data to another station in the network
(MEWNET).
9
F145
P145
Data send
SEND
S1, S2, D, N
Sends the data to the slave station as the MOD
bus master.
9
F146
P146
Data receive
RECV
S1, S2, N, D
Receives the data from the slave station as the
MOD bus master.
9
F145
P145
Data send
SEND
S1, S2, D, N
Sends the data to the slave station as the
MEWTOCOL master.
9
F146
P146
Data receive
RECV
S1, S2, N, D
Receives the data from the slave station as the
MEWTOCOL master.
9
F147
Printout PR
S, D
Converts the ASCII code data in the area starting
with “S” for printing, and outputs it to the word
external output relay WY specified by “D”.
5
F148
P148
Self-
diagnostic
error set
ERR
PERR
n
(n: k100 to
K299)
Stores the self-diagnostic error number “n” in
(DT9000 for FP0/FP-e/FP1/FP-M/FP3 or DT90000
for FP0 T32/FP
Σ
/FP2/FP2SH/FP10SH), turns
R9000 on, and turns on the ERROR LED.
3
Содержание FP0 Series
Страница 14: ...Table of Contents FP0 xii ...
Страница 16: ...Overview FP0 1 2 ...
Страница 82: ...S LINK Control Unit FP0 4 2 ...
Страница 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Страница 96: ...I O Allocation FP0 5 2 ...
Страница 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Страница 102: ...Installation FP0 6 2 ...
Страница 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Страница 114: ...Wiring FP0 7 2 ...
Страница 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Страница 200: ...General use Serial Communications FP0 10 2 ...
Страница 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Страница 220: ...Specifications FP0 12 2 ...
Страница 234: ...Dimensions FP0 13 2 ...
Страница 241: ...Dimensions FP0 13 9 13 6 Detailed Specifications of Cables 13 6 Detailed Specifications of Cables ...
Страница 243: ...Chapter 14 Appendix ...
Страница 380: ...14 138 14 7 ASCII Codes ...