Precautions During Programming
FP0
8
−
11
8.4
Operation Errors
8.4.3
Dealing with Operation Errors
Procedure:
1.
Check the location of the error.
Check the address where the error occurred, which is stored in DT9017 and DT9018,
and make sure the high
−
level instruction for that address is correct and appropriate.
2.
Clear the error.
Use a programming tool to clear the error. (If the mode selector is set to RUN, RUN will
resume as soon as the error is cleared.)
In FP Programmer
II
, press the following keys.
ACLR
(
−
)
OP
1
1
2
ENT
SHIFT
SC
(DELT)
INST
An error can be cleared by turning the power off and on in PROG. mode, however, the
contents of the operation memory except the hold type data will be cleared.
An error can also be cleared by executing a
F148
(self-diagnostic error set) instruction.
Содержание FP0 Series
Страница 14: ...Table of Contents FP0 xii ...
Страница 16: ...Overview FP0 1 2 ...
Страница 82: ...S LINK Control Unit FP0 4 2 ...
Страница 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Страница 96: ...I O Allocation FP0 5 2 ...
Страница 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Страница 102: ...Installation FP0 6 2 ...
Страница 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Страница 114: ...Wiring FP0 7 2 ...
Страница 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Страница 200: ...General use Serial Communications FP0 10 2 ...
Страница 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Страница 220: ...Specifications FP0 12 2 ...
Страница 234: ...Dimensions FP0 13 2 ...
Страница 241: ...Dimensions FP0 13 9 13 6 Detailed Specifications of Cables 13 6 Detailed Specifications of Cables ...
Страница 243: ...Chapter 14 Appendix ...
Страница 380: ...14 138 14 7 ASCII Codes ...