S
−
LINK Control Unit
FP0
4
−
6
4.2
Specifications
4.2.2
S
−
LINK Controller Specifications
Item
Description
Rated power supply voltage
24V DC +/
−
10% / Allowable ripple p
−
p +/
−
10% max
Rated power supply voltage
24V DC +/
−
10% / Allowable ripple p
−
p +/
−
10% max.
(Supplied from IN 24V IN 0V of the S LINK terminal block)
(Supplied from IN
−
24V, IN
−
0V of the S
−
LINK terminal block)
Current consumption
[S
−
LINK controller current consumption (including D
−
G line current consumption)]
Current consumption
(
*
note 1)
[S LINK controller current consumption (including D G line current consumption)]
24V DC 1.6A max.
[Maximum current which can be supplied (supplied to S
−
LINK unit and I/O devices
[Maximum current which can be supplied (supplied to S
−
LINK unit and I/O devices
from 24V 0V line)] + 24V DC 5A (fuse: 5A)
from 24V
−
0V line)] + 24V DC 5A (fuse: 5A)
Transmission method
Bi
−
directional time
−
divided multiple signal transmission
Synchronization method
Bit synchronization, frame synchronization
Transmission protocol
S
−
LINK protocol
Transmission speed
28.5kbps
Transmission delay time
Max. 10.7ms
Transmission distance
Main signal wire: up to a distance to 200m max (400m when a booster is used)
Transmission distance
Main signal wire: up to a distance to 200m max. (400m when a booster is used)
FAN
−
out (
*
note 2)
320
Connection method
(
*
note 3)
‘T’
−
branch multi
−
drop wiring
No. of input/output points
64 points input/64 points output
Fixed
Display
indicators
Transmission
display (SEND)
Green LED blinks in response to synchronization signals
Error indicator
Red LED light up depending on the error
Error address
display
If the system error occurs, the error address is displayed using the red 7
−
segment
LED.
Notes
1) For detailed information on current consumption, refer to
“Determining the Power Supply” in the “S
−
LINK Design
Manual.”
2) The output capacitance for the D
−
G line of the S
−
LINK
controller and booster is indicated by FAN
−
out, and the input
capacitance from the D
−
G line of the S
−
LINK configuration
unit is indicated by FAN
−
in. When configuring the S
−
LINK
system, the configuration should be set up so that the
FAN
−
out total > or = the FAN
−
in total. (For detailed information
on calculating the FAN
−
in value and other values, see the
“S
−
LINK Design Manual.”
3) The FP0 S
−
LINK control unit does not have a loop wiring
function.
Содержание FP0 Series
Страница 14: ...Table of Contents FP0 xii ...
Страница 16: ...Overview FP0 1 2 ...
Страница 82: ...S LINK Control Unit FP0 4 2 ...
Страница 95: ...Chapter 5 I O Allocation 5 1 I O Number 5 3 5 2 Control Unit 5 4 5 3 Expansion I O Unit 5 5 ...
Страница 96: ...I O Allocation FP0 5 2 ...
Страница 100: ...I O Allocation FP0 5 6 5 3 Expansion I O Unit ...
Страница 102: ...Installation FP0 6 2 ...
Страница 112: ...Installation FP0 6 12 6 5 Installation Using FP0 Flat Type Mounting Plate ...
Страница 114: ...Wiring FP0 7 2 ...
Страница 198: ...High speed Counter Pulse Output PWM Output FP0 9 34 9 5 PWM Output Function ...
Страница 200: ...General use Serial Communications FP0 10 2 ...
Страница 210: ...Self Diagnostic and Troubleshooting FP0 11 2 ...
Страница 220: ...Specifications FP0 12 2 ...
Страница 234: ...Dimensions FP0 13 2 ...
Страница 241: ...Dimensions FP0 13 9 13 6 Detailed Specifications of Cables 13 6 Detailed Specifications of Cables ...
Страница 243: ...Chapter 14 Appendix ...
Страница 380: ...14 138 14 7 ASCII Codes ...