12.8. Vertical Airflow Direction Control
Auto Control
• When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as shown in the
diagram.
• When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
• During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that condition, the
louver will stop swinging and rest at the upper limit.
Manual Control
• When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in the diagram.
• The louver can be adjusted by pressing the button to the desired louver position.
• When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
12.9. Horizontal Airflow Direction Control
• The horizontal airflow direction louvers can be adjusted manually by hand.
Содержание CS-PC36HKV
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS PC36HKV...
Страница 10: ...10 5 2 Outdoor Unit 5 2 1 CU PC36HKV...
Страница 11: ...11 6 Refrigeration Cycle Diagram...
Страница 12: ...12 7 Block Diagram...
Страница 13: ...13 8 Wiring Connection Diagram...
Страница 14: ...14 9 Electronic Circuit Diagram 9 1 CS PC36HKV...
Страница 15: ...15 9 2 CU PC36HKV...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit...
Страница 17: ...17 10 2 Outdoor Unit...
Страница 18: ...18 10 3 Indicator...
Страница 22: ...22 This can be used for left rear piping and left bottom piping also...
Страница 45: ...45 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry...
Страница 46: ...46 17 2 Operation Characteristics 17 2 1 CS PC36HKV CU PC36HKV...
Страница 47: ...47...
Страница 50: ...50 18 2 Outdoor Unit 18 2 1 CU PC36HKV...
Страница 51: ...51...