11.4.2.3. Cutting And Flaring The Piping
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make flare after inserting the flare nut onto the copper pipes.
11.4.3.
Air Purging Of The Pipings And Indoor Unit
1) Checking a gas leakage
1. Remove the service port cap from 3-way valves.
2. Connect the Manifold gauge set to the service port of liquid side 3-way valve.
3. Connect the Charging Cylinder to the Manifold gauge set and open the valve of the Cylinder.
4. Open the low pressure side valve of the Manifold gauge for approx.10 seconds and then close.
5. Check gas-leakage of the connecting portion of pipings with the gas-leak detector.
<For the left pipings>
1) Measure the pressure.
2) Keep it for 5-10 minutes.
• Ensure if the pressure indicated on the gauge is as same as that of measured at first time.
Содержание CS-PC36HKV
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS PC36HKV...
Страница 10: ...10 5 2 Outdoor Unit 5 2 1 CU PC36HKV...
Страница 11: ...11 6 Refrigeration Cycle Diagram...
Страница 12: ...12 7 Block Diagram...
Страница 13: ...13 8 Wiring Connection Diagram...
Страница 14: ...14 9 Electronic Circuit Diagram 9 1 CS PC36HKV...
Страница 15: ...15 9 2 CU PC36HKV...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit...
Страница 17: ...17 10 2 Outdoor Unit...
Страница 18: ...18 10 3 Indicator...
Страница 22: ...22 This can be used for left rear piping and left bottom piping also...
Страница 45: ...45 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry...
Страница 46: ...46 17 2 Operation Characteristics 17 2 1 CS PC36HKV CU PC36HKV...
Страница 47: ...47...
Страница 50: ...50 18 2 Outdoor Unit 18 2 1 CU PC36HKV...
Страница 51: ...51...