13.3. Test Run (Forced Cooling mode)
• Test run is necessary after installation is completed.
• To enable test run operation, at outdoor PCB, set the DS1 Switch 1 to ON position.
• Press Test Run button for 1 second.
13.3.1.
Valve Error
• During test run, if the 3-way valve is close, valve error is shown on wired remote control.
• This control is to protect the compressor.
• Valve error is detected if comply with conditions below:
- Power is on for the first time and within 5 minutes from compressor starts (However, the unit is considered power on for first
time when compressor starts operating continuously for 7 minutes).
- Indoor heat exchanger temperature at compressor start - 3ºC < current indoor heat exchanger temperature for 1 minute.
- Indoor suction temperature - 3ºC < current heat exchanger temperature for 5 minutes.
Содержание CS-PC36HKV
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS PC36HKV...
Страница 10: ...10 5 2 Outdoor Unit 5 2 1 CU PC36HKV...
Страница 11: ...11 6 Refrigeration Cycle Diagram...
Страница 12: ...12 7 Block Diagram...
Страница 13: ...13 8 Wiring Connection Diagram...
Страница 14: ...14 9 Electronic Circuit Diagram 9 1 CS PC36HKV...
Страница 15: ...15 9 2 CU PC36HKV...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit...
Страница 17: ...17 10 2 Outdoor Unit...
Страница 18: ...18 10 3 Indicator...
Страница 22: ...22 This can be used for left rear piping and left bottom piping also...
Страница 45: ...45 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry...
Страница 46: ...46 17 2 Operation Characteristics 17 2 1 CS PC36HKV CU PC36HKV...
Страница 47: ...47...
Страница 50: ...50 18 2 Outdoor Unit 18 2 1 CU PC36HKV...
Страница 51: ...51...