23
11.3.4.
Connect The Cable To The Indoor Unit
1. The indoor and outdoor connecting cable can be connected without removing the front grille.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4
×
1.5 mm
2
flexible
cord, type designation 245 IEC 57 or heavier cord.
• Ensure the color of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
• Earth lead wire shall be longer than the other lead wires as shown in the figure for the electrical safety in case of the slipping
out of the cord from the anchorage.
• Secure the cable onto the control board with the holder (clamper).
11.3.4.1. Wire Stripping and Connecting Requirement
Terminal screw
Tightening torque N
l
cm {kgf
l
cm)
M3
69~98 {7~10}
M4
157~196 {16~20}
M5
196~245 {20~25}
Содержание CS-PC36HKV
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS PC36HKV...
Страница 10: ...10 5 2 Outdoor Unit 5 2 1 CU PC36HKV...
Страница 11: ...11 6 Refrigeration Cycle Diagram...
Страница 12: ...12 7 Block Diagram...
Страница 13: ...13 8 Wiring Connection Diagram...
Страница 14: ...14 9 Electronic Circuit Diagram 9 1 CS PC36HKV...
Страница 15: ...15 9 2 CU PC36HKV...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit...
Страница 17: ...17 10 2 Outdoor Unit...
Страница 18: ...18 10 3 Indicator...
Страница 22: ...22 This can be used for left rear piping and left bottom piping also...
Страница 45: ...45 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry...
Страница 46: ...46 17 2 Operation Characteristics 17 2 1 CS PC36HKV CU PC36HKV...
Страница 47: ...47...
Страница 50: ...50 18 2 Outdoor Unit 18 2 1 CU PC36HKV...
Страница 51: ...51...