12.10. Outdoor Fan Control
• Outdoor fan speed changes according to outdoor pipe temperature.
•The fan speed is controlled by the timing of turning the outdoor fan ON and OFF within an interval.
•There unit compares current temperature (T2) with previous (2 seconds before) temperature (T1) and decides the outdoor fan
ON time (X).
Outdoor fan ON time (X) is a variable with the range of 200ms to 1600ms or continuosly ON.
• Every 2 minutes, the outdoor pipe temperature is detected and the outdoor unit fan speed is changed automatically.
12.10.1. Outdoor Fan Remaining Heat Removal Control
• When compressor stop, outdoor fan operates at High speed for 1 minute to remove the remaining heat.
Judgement
Outdoor fan ON time (X)
45
°
C T2
X = X + 100ms
40
°
C T2 45
°
C & T2 T1
X = X + 50ms
40
°
C T2 45
°
C & T2 T1
X = X
35
°
C T2 40
°
C
X = X
30
°
C T2 35
°
C & T2 T1
X = X - 50ms
30
°
C T2 35
°
C & T2 T1
X = X
T2
30
°
C
X = X - 50ms
Содержание CS-PC36HKV
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS PC36HKV...
Страница 10: ...10 5 2 Outdoor Unit 5 2 1 CU PC36HKV...
Страница 11: ...11 6 Refrigeration Cycle Diagram...
Страница 12: ...12 7 Block Diagram...
Страница 13: ...13 8 Wiring Connection Diagram...
Страница 14: ...14 9 Electronic Circuit Diagram 9 1 CS PC36HKV...
Страница 15: ...15 9 2 CU PC36HKV...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit...
Страница 17: ...17 10 2 Outdoor Unit...
Страница 18: ...18 10 3 Indicator...
Страница 22: ...22 This can be used for left rear piping and left bottom piping also...
Страница 45: ...45 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry...
Страница 46: ...46 17 2 Operation Characteristics 17 2 1 CS PC36HKV CU PC36HKV...
Страница 47: ...47...
Страница 50: ...50 18 2 Outdoor Unit 18 2 1 CU PC36HKV...
Страница 51: ...51...