70
RPM shift
+0
+20
+40
+70
(ID temp) Pipe
6.0°C
4.0°C
2.0°C
5.0°C
7.0°C
3.0°C
Compressor starts for
≥
5 minutes
▲
T
≤
2.5°C for 2 minutes
Compressor
OFF
Compressor
restart
▲
T = Intake air temperature – Indoor heat exchanger temperature
13.5 Freeze Prevention Control
To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to
compressor.
This control will activate when temperature of indoor heat exchanger falls below 2°C continuously for more than 4
minutes and compressor turn off.
10
Recovery
4 min
2
Indoor Heat
Exchanger
Temperature
(°C)
Compressor
OFF
The current fan speed will change to freeze prevention speed after 70 seconds compressor on. The fan speed
will be increased according to the indoor pipe temperature as below figure: (Applicable for C9KKV and C12KKV
ONLY)
Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
Restart control (Time Delay Safety Control) will be applied in this control if the recovery time is too short.
13.6 Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between
intake air and indoor heat exchanger is 2.5°C or less for continuously 2 minutes, compressor will stop and restart
automatically.
Time Delay Safety Control is activated before the compressor restart.
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
If this condition happens continuously for 5 times within 50 minutes, unit will turn OFF with TIMER LED blinks.
The 5 Times counter can be reset when either one of the following condition happen:
o
Unit is OFF by remote control or AUTO OFF/ON button.
o
Indoor intake temperature – Indoor piping temperature > 5°C for one minute or more.
o
Operation mode change.
The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
TIMER LED blinking will be reset if:
o
Indoor intake temperature – Indoor piping temperature > 5°C for one minute or more.
o
Power supply reset.
Содержание CS-C12MKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9MKV CS C12MKV ...
Страница 14: ...14 5 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9MKV 5 2 2 CU C12MKV ...
Страница 16: ...16 5 2 3 CU C18MKV CU C24MKV CU C28MKV ...
Страница 17: ...17 6 Refrigeration Cycle Diagram ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9MKV CU C9MKV CS C12MKV CU C12MKV ...
Страница 19: ...19 7 1 2 CS C18MKV CU C18MKV CS C24MKV CU C24MKV ...
Страница 20: ...20 7 1 3 CS C28MKV CU C28MKV ...
Страница 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9MKV CU C9MKV ...
Страница 27: ...27 9 2 CS C12MKV CU C12MKV ...
Страница 28: ...28 9 3 CS C18MKV CU C18MKV ...
Страница 29: ...29 9 4 CS C24MKV CU C24MKV ...
Страница 30: ...30 9 5 CS C28MKV CU C28MKV ...
Страница 31: ...31 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS C9MKV CS C12MKV ...
Страница 32: ...32 10 1 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 34: ...34 10 1 6 Human Activity Sensor Printed Circuit Board ...
Страница 46: ...46 12 1 2 Cooling Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 48: ...48 12 2 2 Soft Dry Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 77: ...77 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Страница 79: ...79 Figure 9 Figure 10 ...
Страница 81: ...81 16 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure1 5 ...
Страница 83: ...83 Figure 19 Figure 20 Figure 21 ...
Страница 85: ...85 16 3 1 3 To remove power electronic controller Figure 24 Figure 8 Figure 9 ...
Страница 87: ...87 Figure 30 Figure 31 Figure 32 ...
Страница 88: ...88 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...