61
12.14
E-ion operation
This operation provides clean air by producing negative ions to attract dust captured at the positively charged
active e-ion filters.
e-ion operation start condition
o
During unit running at any operation mode, if “e-ion” operation is selected, combination operation (operation
mode + e-ion operation) starts.
o
During unit is OFF, if “e-ion” operation is selected, e-ion individual operation starts.
e-ion operation stop condition
o
When “OFF/ON” button is pressed to stop the operation.
o
When “PATROL/e-ion” button is pressed.
o
When OFF Timer activates.
e-ion operation pause condition
o
When indoor fan stop (during deice, odor cut control, thermostat off, etc.). e-ion operation resume after
indoor fan restarts.
o
When indoor intake temperature
≥
40°C. e-ion operation resume after indoor intake temperature < 40°C
continuously for 30 minutes.
Indoor
fan
control
o
During any operation mode combines with e-ion operation, fan speed follows respective operation mode.
o
During e-ion individual operation – only Auto Fan Speed and no Powerful operation is allowed. Even if Fan
Speed button is pressed, no signal is sent to air conditioner, and no change on LCD display.
Auto Fan Speed for e-ion operation switches from SHi to Hi after 4 hours of operation.
Airflow direction control
o
During any operation mode combines with e-ion operation, airflow direction follows respective operation
mode.
o
During e-ion individual operation, only Auto Air Swing is allowed. Even if Air Swing button is pressed, no
signal is sent to air conditioner, and no change on LCD display.
Timer
control
o
When ON timer activates when unit stops, previous operation resumes and restored last saved e-ion
operation status.
o
When ON timer activates during any operation, no change and carry on current operation.
o
When OFF timer activates during any operation, all operation stops and the latest e-ion operation status is
saved.
Indicator
o
When e-ion operation starts, e-ion indicator ON.
Remote Control Receiving Sound
o
Normal
Operation
Î
e-ion Operation
: Beep
o
e-ion
Operation
Î
Normal Operation
: Beep
o
Stop
Î
e-ion individual Operation
: Beep
o
e-ion individual Operation
Î
Stop
:
Long
Beep
Power
failure
o
During e-ion individual operation, if power failure occurs, after power resumes, e-ion individual operation
resumes immediately.
o
During combination operation, if power failure occurs, after power resumes, combination operation resume
immediately.
o
e-ion operation status is not memorized after OFF the unit. After OFF, when the operation is ON again, air
conditioner operates without e-ion operation.
Содержание CS-C12MKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9MKV CS C12MKV ...
Страница 14: ...14 5 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9MKV 5 2 2 CU C12MKV ...
Страница 16: ...16 5 2 3 CU C18MKV CU C24MKV CU C28MKV ...
Страница 17: ...17 6 Refrigeration Cycle Diagram ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9MKV CU C9MKV CS C12MKV CU C12MKV ...
Страница 19: ...19 7 1 2 CS C18MKV CU C18MKV CS C24MKV CU C24MKV ...
Страница 20: ...20 7 1 3 CS C28MKV CU C28MKV ...
Страница 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9MKV CU C9MKV ...
Страница 27: ...27 9 2 CS C12MKV CU C12MKV ...
Страница 28: ...28 9 3 CS C18MKV CU C18MKV ...
Страница 29: ...29 9 4 CS C24MKV CU C24MKV ...
Страница 30: ...30 9 5 CS C28MKV CU C28MKV ...
Страница 31: ...31 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS C9MKV CS C12MKV ...
Страница 32: ...32 10 1 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 34: ...34 10 1 6 Human Activity Sensor Printed Circuit Board ...
Страница 46: ...46 12 1 2 Cooling Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 48: ...48 12 2 2 Soft Dry Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 77: ...77 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Страница 79: ...79 Figure 9 Figure 10 ...
Страница 81: ...81 16 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure1 5 ...
Страница 83: ...83 Figure 19 Figure 20 Figure 21 ...
Страница 85: ...85 16 3 1 3 To remove power electronic controller Figure 24 Figure 8 Figure 9 ...
Страница 87: ...87 Figure 30 Figure 31 Figure 32 ...
Страница 88: ...88 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...