56
o
RPM control during Hi & Me cool
Auto Fan Speed
Quiet operation stops when:
o
Quiet button is pressed again.
o
Stopped by OFF/ON operation button.
o
Timer OFF activates.
o
Operation mode button is changed.
12.10
Timer Control
12.10.1 ON Timer
When the ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so
that the room will reach nearly to the set temperature by the set time.
For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
For Automatic operation, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time
to detect the intake air temperature to determine the operation mode. The power LED will blink.
12.10.2 OFF Timer
When the OFF Timer is set using the remote control, the unit will stop operate according to the desired setting.
Notes:
1 By pressing ON/OFF operation button, the ON Timer or OFF Timer will not be cancel.
2 To cancel the previous timer setting, press CANCEL button.
3 To activate the previous timer setting, press SET button.
4 If main power supply is switched off, the Timer setting will be cancel.
12.11 Random Auto Restart Control
If there is a power failure during operation, the air conditioner will automatically restart after 3 to 4 minutes when
the power is resumed.
It will start with previous operation mode and airflow direction.
If there are more than one air conditioner unit in operation and power failure occur, restart time for each unit to
operate will be decided randomly using 4 parameters:- intake air temperature, setting temperature, fan speed
and air swing louver position.
This Random Auto Restart Control is not available when Timer is set.
This control can be omitted by open the circuit of JX02 at indoor unit printed circuit board.
12.12 Remote Control Signal Receiving Sound
Short beep sound will be heard when turn ON the air conditioner or enabling other operations.
Long beep sound will be heard when turn OFF the air conditioner or disabling other operations.
Содержание CS-C12MKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9MKV CS C12MKV ...
Страница 14: ...14 5 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9MKV 5 2 2 CU C12MKV ...
Страница 16: ...16 5 2 3 CU C18MKV CU C24MKV CU C28MKV ...
Страница 17: ...17 6 Refrigeration Cycle Diagram ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9MKV CU C9MKV CS C12MKV CU C12MKV ...
Страница 19: ...19 7 1 2 CS C18MKV CU C18MKV CS C24MKV CU C24MKV ...
Страница 20: ...20 7 1 3 CS C28MKV CU C28MKV ...
Страница 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9MKV CU C9MKV ...
Страница 27: ...27 9 2 CS C12MKV CU C12MKV ...
Страница 28: ...28 9 3 CS C18MKV CU C18MKV ...
Страница 29: ...29 9 4 CS C24MKV CU C24MKV ...
Страница 30: ...30 9 5 CS C28MKV CU C28MKV ...
Страница 31: ...31 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS C9MKV CS C12MKV ...
Страница 32: ...32 10 1 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 34: ...34 10 1 6 Human Activity Sensor Printed Circuit Board ...
Страница 46: ...46 12 1 2 Cooling Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 48: ...48 12 2 2 Soft Dry Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 77: ...77 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Страница 79: ...79 Figure 9 Figure 10 ...
Страница 81: ...81 16 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure1 5 ...
Страница 83: ...83 Figure 19 Figure 20 Figure 21 ...
Страница 85: ...85 16 3 1 3 To remove power electronic controller Figure 24 Figure 8 Figure 9 ...
Страница 87: ...87 Figure 30 Figure 31 Figure 32 ...
Страница 88: ...88 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...