12.2 Soft Dry Operation
Soft Dry operation can be set using remote control.
Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
This operation starts when the intake air temperature sensor reaches the setting temperature on the remote
control.
When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be
turn “OFF” for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the
setting temperature as shown in figure below.
However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the
indoor unit will start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON”
point.
12.2.1 Soft Dry Operation Time Diagram (For CS-C9MK CU-C9MK and CS-C12MK
CU-C12MK)
Содержание CS-C12MKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9MKV CS C12MKV ...
Страница 14: ...14 5 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9MKV 5 2 2 CU C12MKV ...
Страница 16: ...16 5 2 3 CU C18MKV CU C24MKV CU C28MKV ...
Страница 17: ...17 6 Refrigeration Cycle Diagram ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9MKV CU C9MKV CS C12MKV CU C12MKV ...
Страница 19: ...19 7 1 2 CS C18MKV CU C18MKV CS C24MKV CU C24MKV ...
Страница 20: ...20 7 1 3 CS C28MKV CU C28MKV ...
Страница 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9MKV CU C9MKV ...
Страница 27: ...27 9 2 CS C12MKV CU C12MKV ...
Страница 28: ...28 9 3 CS C18MKV CU C18MKV ...
Страница 29: ...29 9 4 CS C24MKV CU C24MKV ...
Страница 30: ...30 9 5 CS C28MKV CU C28MKV ...
Страница 31: ...31 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS C9MKV CS C12MKV ...
Страница 32: ...32 10 1 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 34: ...34 10 1 6 Human Activity Sensor Printed Circuit Board ...
Страница 46: ...46 12 1 2 Cooling Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 48: ...48 12 2 2 Soft Dry Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 77: ...77 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Страница 79: ...79 Figure 9 Figure 10 ...
Страница 81: ...81 16 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure1 5 ...
Страница 83: ...83 Figure 19 Figure 20 Figure 21 ...
Страница 85: ...85 16 3 1 3 To remove power electronic controller Figure 24 Figure 8 Figure 9 ...
Страница 87: ...87 Figure 30 Figure 31 Figure 32 ...
Страница 88: ...88 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...