58
Patrol Sensor Control
o
First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness
level is monitored. The Air Dirtiness level is set to Clean, Patrol LED turns blue color.
o
After that, Patrol sensor starts to record the resistance value at fixed interval. Higher resistance value
indicates cleaner air.
o
The air dirtiness level is monitored by comparing the current resistance value with maximum resistance value
from time to time to get the Air Dirtiness Value.
o
There are 3 air dirtiness level, based on the Air Dirtiness Value:
Air Dirtiness level 0: Clean
– Patrol LED = blue color
Air Dirtiness level 1: Moderate
– Patrol LED = orange color
Air Dirtiness level 2: Contaminated – Patrol LED = red color
Air Dirtiness Level 0
Air Quality Worsen
G1
Air Dirtiness Level 1
G3
G2
G4
Air Dirtiness Level 2
Air Quality Improve
Dirtiness level sensitivity adjustment
It is possible to change the Patrol sensor sensitivity, where the Threshold value (G1 ~ G4) will be shifted
accordingly:
1 Press and release “SET” button.
2 Press
Timer
▲
/ Timer
▼
button to select sensitivity.
(Air 1 “Low Sensitivity”
↔
Air 2 “Standard” (Default)
↔
Air 3 “High Sensitivity”)
3 Confirm setting by pressing “Timer Set” button. LCD returned to original display after 2 seconds.
4 LCD returned to original display if remote control does not operate for 30 seconds
e-ion
Control
o
e-ion operation starts condition
When dirtiness at level 2 (Patrol LED turns red).
2 minutes after stabilization time (Patrol LED turns red).
4 hours at level 0 (Patrol LED turns red).
o
e-ion operation time
If dirtiness level improves from level 2 to level 1 (Patrol LED from red to orange), the unit carries out level
change after 60 seconds.
When dirtiness level returns to level 0 (Patrol LED turns blue) continuously for 11 minutes or more, e-ion
operation stops.
Dirtiness Level and fan speed
o
When e-ion operation starts, the fan speed increases based on dirtiness level:
rpm shift
Dirtiness level
Patrol individual
operation
Combine operation
Dirtiness level 0
No change
No change
Auto
Manual
Dirtiness level 1
+ 20
+1 fan tap (max - Hi)
e-ion ON
Dirtiness level 2
+ 40
No change
Me -
Me
+2 fan tap (max - Hi)
o
Indoor Fan Control
During any operation mode combines with Patrol operation, fan speed follows respective operation mode.
During Patrol individual operation if e-ion starts, only Auto Fan Speed and no Powerful operation is
allowed. Even if “Fan Speed” button is pressed, no signal is sent to air conditioner, and no change on
LCD display.
During Patrol individual operation if e-ion stops, Indoor Fan stop operation.
Air Dirtine
ss Value
Dirty
Moderate
Clean
Содержание CS-C12MKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9MKV CS C12MKV ...
Страница 14: ...14 5 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9MKV 5 2 2 CU C12MKV ...
Страница 16: ...16 5 2 3 CU C18MKV CU C24MKV CU C28MKV ...
Страница 17: ...17 6 Refrigeration Cycle Diagram ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9MKV CU C9MKV CS C12MKV CU C12MKV ...
Страница 19: ...19 7 1 2 CS C18MKV CU C18MKV CS C24MKV CU C24MKV ...
Страница 20: ...20 7 1 3 CS C28MKV CU C28MKV ...
Страница 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9MKV CU C9MKV ...
Страница 27: ...27 9 2 CS C12MKV CU C12MKV ...
Страница 28: ...28 9 3 CS C18MKV CU C18MKV ...
Страница 29: ...29 9 4 CS C24MKV CU C24MKV ...
Страница 30: ...30 9 5 CS C28MKV CU C28MKV ...
Страница 31: ...31 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS C9MKV CS C12MKV ...
Страница 32: ...32 10 1 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Страница 34: ...34 10 1 6 Human Activity Sensor Printed Circuit Board ...
Страница 46: ...46 12 1 2 Cooling Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 48: ...48 12 2 2 Soft Dry Operation Time Diagram For CS C18MK CU C18MK CS C24MK CU C24MK and CS C28MK CU C28MK ...
Страница 77: ...77 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Страница 79: ...79 Figure 9 Figure 10 ...
Страница 81: ...81 16 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure1 5 ...
Страница 83: ...83 Figure 19 Figure 20 Figure 21 ...
Страница 85: ...85 16 3 1 3 To remove power electronic controller Figure 24 Figure 8 Figure 9 ...
Страница 87: ...87 Figure 30 Figure 31 Figure 32 ...
Страница 88: ...88 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...