130
Aquarea air / water heat pump – design handbook 07 / 2014
Appendix
Cooling capacity in relation to supply water and and outside temperature
Aquarea LT
Aquarea LT
Cooling capacity in relation to supply water and and outside temperature
Outside temperature
Supply water temperature
Models
7
14
18
3 kW (single phase)
WH-SDC03E3E5
5 kW (single phase)
WH-MDC05F3E5
5 kW (single phase)
WH-SDC05E3E5
7 kW (single phase)
WH-SDC07C3E5
18
2 .4
4 .4
3 .7
25
3 .2
4 .1
3 .5
35
3 .2
3 .9
3 .3
43
2 .9
3 .5
3 .0
7
14
18
18
2 .0
2 .2
2 .5
25
5 .0
6 .3
6 .3
35
4 .5
5 .1
5 .0
43
3 .8
4 .5
4 .3
7
14
18
18
4 .5
5 .0
5 .7
25
5 .0
6 .3
5 .4
35
4 .5
5 .5
5 .0
43
3 .3
4 .1
4 .4
7
14
18
18
5 .1
25
6 .6
35
6 .0
7 .3
8 .0
43
5 .1
7
14
18
9 kW (single phase)
WH-SDC09C3E5
18
5 .9
25
7 .8
35
7 .0
8 .3
9 .0
43
6 .2
7
14
18
9 kW (single and three phase)
WH-MDC09
WH-SDC09C6E8
18
5 .9
25
7 .5
35
7 .0
8 .3 / 8 .6
9 .0 / 9 .5
43
5 .8
7
14
18
12 kW (single and three phase)
WH-MDC12 /
WH-SDC12
18
7 .7
25
9 .2
35
10 .0
11 .6 / 11 .8
12 .5 / 12 .8
43
7 .6
7
14
18
14 kW (single and three phase)
WH-MDC14 /
WH-SDC14
18
8 .9
25
10 .0
35
11 .5
12 .8 / 13 .4
13 .5 / 14 .5
43
9 .1
7
14
18
16 kW (single and three phase)
WH-MDC16 /
WH-SDC16
18
9 .6
25
10 .5
35
12 .2
13 .4 / 14 .6
14 .1 / 16 .0
43
10 .1
Cooling capacity [kW] of individual models of the
split and monobloc systems
for different outside temperatures
and a supply water temperature of 7 °C.