128
Aquarea air / water heat pump – design handbook 07 / 2014
Appendix
Heating capacity in relation to supply water and outside temperature
Aquarea HT
Outside temperature
Supply water temperature
Models
30
35
40
45
50
55
60
65
9 kW (single phase)
WH-SHF09F3E5¹
WH-SHF09D3E5
(Phase-out models)
-15
9 .0
9,0
8,9
8,8
8,5
8,5
8,0
7,8
-7
9,0
9,3
9,0
8,9
8,9
9,3
8,9
8,9
2
9,0
8,9
9,0
8,3
9,0
9,0
9,0
9,0
7
9,0
9,2
9,0
9,2
9,0
8,8
9,0
9,0
25
12,0
12,0
12,0
10,8
10,2
11,2
10,0
9,8
30
35
40
45
50
55
60
65
12 kW (single phase)
WH-SHF12F6E5¹
WH-SHF12D6E5
(Phase-out models)
-15
12,0
11,2
11,0
10,6
10,3
9,7
9,0
8,0
-7
12,0
11,9
11,5
11,2
10,8
10,2
9,9
9,6
2
12,0
11,5
11,5
10,5
11,0
10,8
10,7
10,3
7
12,0
11,6
12,0
11,5
12,0
11,7
12,0
12,0
25
12,0
12,0
12,0
12,0
12,0
12,0
12,0
12,0
30
35
40
45
50
55
60
65
9 kW (three phase)
WH-SHF09F3E8¹
WH-SHF09D3E8
(Phase-out models)
-15
9,0
9,0
8,9
8,8
8,5
8,5
8,0
7,8
-7
9,0
9,0
9,0
8,9
8,9
8,9
8,9
8,9
2
9,0
9,0
9,0
9,0
9,0
9,0
9,0
9,0
7
9,0
9,0
9,0
9,0
9,0
9,0
9,0
9,0
25
12,0
12,0
12,0
10,8
10,2
11,2
10,0
9,8
30
35
40
45
50
55
60
65
12 kW (three phase)
WH-SHF12F9E8¹
WH-SHF12D9E8
(Phase-out models)
-15
12,0
12,0
11,0
10,6
10,3
9,7
9,0
8,0
-7
12,0
12,0
11,5
11,2
10,8
10,1
9,9
9,6
2
12,0
12,0
11,5
11,3
11,0
10,8
10,7
10,3
7
12,0
12,0
12,0
12,0
12,0
12,0
12,0
12,0
25
12,0
12,0
12,0
12,0
12,0
12,0
12,0
12,0
Heating capacity [kW] of individual models of the
bi-bloc system
for different supply water and outside temperatures [°C].
¹
Preliminary specifications