4-12
Installation
and Wiring
4.3 Safety Measures
4.3.1 Safety Circuit
Precautions regarding system design
In certain applications, malfunction may occur for the following reasons:
-
Power on timing differences between the PLC system and input/output or
mechanical power apparatus.
-
Response time lag when a momentary power drop occurs.
-
Abnormality in the PLC unit, external power supply, or other devices.
In order to prevent a malfunction resulting in system shutdown take the following measures as
adequate:
Install the interlock circuit outside PLC
When a motor clockwise/counter-clockwise operation is controlled, provide an interlock
circuit externally.
Install the emergency stop circuit outside PLC
Install an emergency stop circuit outside PLC to turn off power supply to the output device.
Start up other devices before PLC
The PLC should be started after booting the I/O device and mechanical power apparatus.
When stopping the operation of PLC, have the input/output devices turned off after PLC has
stopped operating.
Install safety measures in case of alarm outside the PLC body
When an alarm is released, PLC output is turned off and its operation is stopped. In order to
prevent a malfunction resulting in system shutdown under the above conditions, install safety
measures outside PLC.
Perform secure grounding
When installing PLC next to devices that generate high voltages from switching, such as
inverters, do not ground them together. Use an exclusive ground for each device which
should be grounded at a grounding resistance of 100
Ω
or less.
4.3.2 Momentary Power Drop
Operation in the case of momentary power drop varies depending on the combination of units,
the power supply voltage, and other factors. In some cases, operation may be the same as
that for a power supply reset.
When a power supply unit (AC) is being used, operation is continued in the case of
momentary power drop shorter than 10 ms.
When 24V DC is being supplied to the CPU unit, operation is continued in the case of
momentary power drop shorter than 4 ms.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание AFP7PSA1
Страница 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 9: ...1 Overview Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 19: ...2 Names and Functions of Parts Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 23: ...3 I O Number Allocation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 33: ...4 Installation and Wiring Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 46: ...4 14 Installation and Wiring Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 47: ...5 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 62: ...5 16 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 63: ...6 Troubleshooting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 70: ...6 8 Troubleshooting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 71: ...7 Maintenance and Inspection Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 76: ...7 6 Maintenance and Inspection Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 77: ...8 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...