Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
29
12
Operation
The LED "Operation" (L6) is indicating if the "Alert Annunciation"
function is enabled or disabled
25
.
When the "Alert Annunciation" function is enabled, the LED "L3"
(Fire brigade alerted) is indicating if it is an
AA
alarm or not.
Off =
AA
alarm. On = no
AA
alarm / Output "Fire brigade tx"
activated.
The LED "L4" (Acknowledged) is indicating if the
AA
alarm has been
acknowledged.
The following page / figure show an operation summary for the Alert
Annunciation units 1735 & 1736.
See also chapter "SW mode & Address setting, page 16.
AA
alarm acknowledged in any Alert Annunciation unit will be
indicated in all "Alert annunciation units".
AA
alarm reset in any Alert annunciation unit (or in the c.i.e.) will
also be "reset" in all other Alert Annunciation units.
NOTE!
The Alert Annunciation unit in the figure is only schematic,
i.e. the positions of the different LEDs, push buttons, etc. are not
according to Figure 3, on page 10.
25
The AA function is normally enabled (during daytime) / disabled (during
night-time) via a time channel.