Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
11
Table of LED indicators:
LED indicator
Colour
Indicating
L1
Alarm (Larm)
2 x Red
B
LED
"L6"
turned on
+ Buzzer
(interm.)
AA
alarm (Acknowledge time starts.)
B
LED
"L3"
turned on
(no
buzzer).
Fire alarm (i.e. not an
AA
alarm).
Cont. (no
buzzer)
AA
alarm(s) is/are acknowledged.
L2
Alarms queued
(Flera larm)
2 x Red
Blinking
More than one alarm. Use push button
"P1" (Alarms queued) to scroll.
L3
Fire brigade alerted
(Räddningstjänsten
larmad)
Red
Cont.
Output(s) for "Fire brigade tx" are
activated.
5
L4
Acknowledge
(Kvittering)
Yellow
Cont.
All
AA
alarms have been acknowledged
by the push button "P2" (Acknowledge)
and new
AA
alarms will be
automatically acknowledged.
L5
-
-
-
-
L6
Operation (Drift)
Green
Cont.
The
AA
function is enabled.
Off
The
AA
function is not enabled.
NOTE!
Regarding "L2", see also chapter "SW mode & Address
setting, page 16.
5
Indicating the same way as in the c.i.e. the
AA
unit is connected to, i.e. by
activated output(s) of the corresponding type or an activated input.