Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
17
the unit will automatically be ready for the "Address setting ", see
below.
6.1.1
SW mode setting via jumper "J4"
An
AA
unit
in operation
15
will be ready for the "SW mode setting"
via the jumper "J4" in the unit. Activate "J4"
momentarily
.
16
When the
AA
unit is ready for the "SW mode setting" this is indicated
by the LED "L2" (Alarms queued). The back-light is turned on and
the following information is shown in the display:
MODE SETTING! Change = Black
Type: xxxxxxxxxxxx Store = Yellow
Continue in accordance with chapter "SW mode setting", page 16.
6.2
Address setting
After the SW mode setting, the
AA
unit is ready for the "address
setting".
As an alternative, an
AA
unit
in operation
17
can be ready for the
"address setting" directly via a c.i.e. menu. See the following chapter.
When the
AA
unit is ready for the "address setting" this is indicated
by the LED "L2" (Alarms queued). The back-light is turned on and
the following information is shown in the display:
ADDRESS SETTING Change = Black
Address: XX Store = Yellow
XX
can be changed to the following:
For an
AA
unit, the address can be set to
00-15
.
18
(Default is "00".)
Scroll to the wanted address with the push button "P1" (black). Store
the selected address with the push button "P2" (yellow) and the unit
will automatically restart and enter its normal operation mode.
19
6.2.1
Address setting mode via the c.i.e.
A specific
AA
unit
or
all the
AA
units connected to the same line
(RS485) can, in normal operation, from the c.i.e. receive a command
and get ready for the "Address setting" directly. This is done via
16
If "J4" is not removed, the
AA
unit will not enter its normal operation
mode after the restart but start from the beginning again, ready for the SW
mode setting.
17
Or all the
AA
units connected to the same Ext. FBP / DU interface board
1587.
18
This is the max. no. of addresses. The max. no. of units connected to a
board is depending on the type of units and if ext. power supply is used.
19
If the unit has no SW mode, i.e. "Not selected", it will not enter its normal
operation mode after the restart but start from the beginning again, ready for
the SW mode setting.