Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
20
7
User definable text messages
(alarm texts)
In the c.i.e., each alarm point (zone – address) and each zone can have
an individual user definable text message (alarm text)
21
presented in
the display by fire alarm, see the Planning and Operating Instructions
for the system respectively.
The user definable text messages shown in the c.i.e. will also be sent
to each Alert Annunciation Unit and shown in its display.
As an alternative, text messages for all or selected alarm points / zones
can be stored in each
AA
unit.
22
If so, these text messages will be
shown instead of the text messages sent out from the c.i.e.
The priority order is as follows:
1.
Point alarm text stored in the
AA
unit.
2.
Zone alarm text stored in the
AA
unit.
3.
Default alarm text stored in the
AA
unit.
4.
Text sent out from the c.i.e.
When alarm texts shall be stored in all or in some
AA
units, the
unique alarm texts are created in Win512 / Win128 / Win512 G3 and
downloaded when the c.i.e. site specific data (SSD) is downloaded.
NOTE!
It is also possible to select which fire alarms that shall be
presented in the
AA
unit respectively, see chapter "Selective Fire
alarm presentation", page 8.
21
Each alarm text (up to 40 alphanumeric characters) will be shown on the
second row. The text messages are created and downloaded via Win512 /
Win128 / Win512 G3.
22
At least 617 text messages can be stored in each unit.