32
Comments to the components:
F3
1.5 A fuse (not replaceable; the whole p.c.b. should be
replaced).
J1
Terminal block for the unit's connections.
J2
"D" connector (9 ways, male), RS232 interface for SW
download.
(Note, jumpers "JP3" and "JP4" have to be in pos. "A".)
J3
Not used in this unit.
J4
Used when SW mode and address setting shall be done.
J8
Not used in this unit.
J10
Not used in this unit.
J11
Not used in this unit.
JP1
Reset. (Restart of the unit.)
JP2
Boot. (The unit has to be in "bootstrap" mode before SW
download.)
JP3
Pos. "A": PC, for SW download, connected via "J2".
Pos. "B": The unit is connected to the c.i.e. (default).
JP4
Pos. "A": PC, for SW download, connected via "J2".
Pos. "B": The unit is connected to the c.i.e. (default).
JP8
Used when the unit is the last unit on the line, i.e. to
connect the built-in end-of- line resistor (120R).
JP9
For future use.
KEY1LED1
Connector for the front panel.
P1
Potentiometer for LCD contrast adjustment.