6.1. Pressure fan work parameters.

Fan power [Π100]

- this value defines power of the fan. When „Πr” parameter is set to

„0-10” this is the maximum power of the fanwhich can be achieved during automatic

fan control.

Minimum fan power [n 40]

- lowest fan power which can be used when automatic

fan speed control is on and when fan speed is gradually increased during boiler start.

Fan speed decrease coefficient [Πh10]

- this parameter influences the way fan

speed is reduced when boiler tremperature is approaching its desired value. E.g.

setting this parameter to 2 means that when the controller is in WORK mode and

boiler temperature is 2°C lower than desired boiler temperature the fan will work with

its maximum power [Π100]. Further increase of boiler temperature will cause fan

speed to be reduced gradually to its minimum power [n 40].

Automatic fan speed control [Πr 1]

- it is on, when this parameteris set to „0-10” and

causes automatic fan speed decrease when temperature of water in the boiler reaches

desired temperature.If this parameter is set to „-”, the fan automatic smooth speed

control is disabled and the fan can work with power set by „Π” parameter. Setting

parameter value in range from 0 to 10 means time in minutes of the smooth fan speed

increase from 40% to value of „Π” for smooth boiler start.

Fan work time [Πn 5]

- time of turning the fan on for a while, to remove accumulated

gases. Setting the parameter to „-” turns this function off. This function can be active in

WORK mode.

Fan pause time [Πu 6]

- time between fan work periods

Fan work time in manual mode [Πd 3]

– this parameter defines how long the fan will

work when started manually. Setting this parameter to „--” will disable manual fan

operation.

6.2. Central heating pump parameters.

Central heating pump launch temperature [P 65]

- temperature of water in the

boiler, which causes

start of the circulating pump. Circulating pump works

independently from the control process and is launched additionally in case of boiler

overheat.

Central heating pump hysteresis [Ph 5]

- this parameter defines what value should

temperature decrease by, below circulating pump launch temperature, to turn the

pump off.

Central heating pump work mode [Pr 1]

- central heating pump, independently of

work mode, is always turned off when boiler temperature drops below temperature set

with

[P 65]

parameter and is always turned when boiler temperature exceeds 90°C,

boiler is overheated or boiler temperature sensor is damaged. In remaining cases,

central heating pump works in mode set with

[Pr ]

parameter:

Содержание RK-2001AT2

Страница 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001AT2 Version AC22...

Страница 2: ...r starts in HEATING UP mode This mode turns off influence of exhaust gas thermostat on the fan and central heating pump HEATING UP is active until exhaust gas temperature achieves temperature set with...

Страница 3: ...shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if the screws of the connector are properly screwed CA...

Страница 4: ...on stops the fan for example allowing to add fuel to the boiler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode...

Страница 5: ...splays current measured room or exhaust gas temperature 6 Setting up the parameters service mode Holding OK button for more than 3 seconds causes change to service mode where you can view and change p...

Страница 6: ...ng pump turn off delay 1 99 1min 2 L 65 Minimum boiler temperature 60 65 1 C 65 H 90 Maximum boiler temperature 80 95 1 C 90 h 5 Boiler temperature hysteresis 1 10 1 C 5 A105 Boiler overheating temper...

Страница 7: ...meter value in range from 0 to 10 means time in minutes of the smooth fan speed increase from 40 to value of for smooth boiler start Fan work time n 5 time of turning the fan on for a while to remove...

Страница 8: ...ion Central heating pump turn off delay Pd 2 central heating pump stopping too early can cause temperature rise in the boiler and cause its overheating This parameter allows setting central heating pu...

Страница 9: ...described above When contacts are open the controller will keep minimum boiler temperature Attention When external thermostat is connected in place of room temperature sensor the temperature set with...

Страница 10: ...ing boiler start Fuel shortage testing time in work mode Fb30 time set with this parameter is used when testing fuel shortage after boiler has started Setting this parameter to disables fuel shortage...

Страница 11: ...are working correctly After detection of fault it stops the pressure fan turns on the circulating pump and shows proper error message on the display In case of failure please turn off the controller p...

Страница 12: ...urement range 9 109 C 1 C Boiler temperature adjustment range 30 90 C 1 C Programmable boiler overheating protection 90 99 C 1 C Hardware boiler overheating protection 95 C 1 C Circulating pump launch...

Страница 13: ...13 Picture 2 RK 2001AT2 connection scheme Picture 3 UM 1 module connection scheme...

Страница 14: ...controller work mode Pc Central heating pump pause time Pd 2 Central heating pump turn off delay L 65 Minimum boiler temperature H 90 Maximum boiler temperature h 5 Boiler temperature hysteresis A105...

Страница 15: ......

Страница 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Отзывы: