background image

11

6.9. Testing of device's outputs.

To make checking the controller work easier, it is possible to test output circuits

which control the fan and the pump, and the circuit which controls additional boiler. By

choosing

[outP]

on the display and pressing OK button you can turn on the circulating

pump for a while, by choosing

[outΠ]

and pressing OK you can turn on the pressure

fan and by choosing

[outr]

and pressing OK you can turn the additional boiler, the

alarm signaling system or the mixing valve servo-motor on (if the additional module is

connected).

6.10. Factory defaults.

You can return to standard settings, set by the producer, by choosing

[Prod]

option

in service mode and pressing OK button. After activating this function, the device sets

each parameter showed in the table to default.

6.11. Exiting service mode.

By choosing

[End ]

option on the display and pressing OK button you can quit

service mode. The device also quits service mode, when no buttons are pressed for 1

minute.

7. Device failures.

The controller is constantly testing if its internal circuits and temperature sensor are

working correctly. After detection of fault, it stops the pressure fan, turns on the

circulating pump and shows proper error message on the display. In case of failure

please turn off the controller, plug the circulating pump to the power source, bypassing

the controller, ensure appropriate fuel firing in the boiler and contact the service.

When

[E 1]

error appears on the display, it means fault (short-circuit) in the boiler

sensor circuit or temperature below -9°C.

[E 2]

is displayed if boiler overheats.

[E 3]

error means fault and overheating at the same time. Appearing of

[E 1]

error on the

display without ability to cancel it by pressing STOP button, in spite of temperature

below 90°C, may mean permanent damage of boiler temperature sensor (e.g. if the

boiler overheated above 150°C).

[E 8]

error on the display indicated malfunction in

exhaust gas sensor circuit. In this case the controller disables exhaust gas thermostat

(it will behave as if exhaust gas temperature was always higher than temperature set

with additional thermostat knob).

8. Device removal.

In case of need to remove the controller from the system:

- turn the master switch off,

- disconnect the power of the boiler,

- remove the controller from the slot in the boiler,

- disconnect all connectors with cords from the controller.

Содержание RK-2001AT2

Страница 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001AT2 Version AC22...

Страница 2: ...r starts in HEATING UP mode This mode turns off influence of exhaust gas thermostat on the fan and central heating pump HEATING UP is active until exhaust gas temperature achieves temperature set with...

Страница 3: ...shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if the screws of the connector are properly screwed CA...

Страница 4: ...on stops the fan for example allowing to add fuel to the boiler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode...

Страница 5: ...splays current measured room or exhaust gas temperature 6 Setting up the parameters service mode Holding OK button for more than 3 seconds causes change to service mode where you can view and change p...

Страница 6: ...ng pump turn off delay 1 99 1min 2 L 65 Minimum boiler temperature 60 65 1 C 65 H 90 Maximum boiler temperature 80 95 1 C 90 h 5 Boiler temperature hysteresis 1 10 1 C 5 A105 Boiler overheating temper...

Страница 7: ...meter value in range from 0 to 10 means time in minutes of the smooth fan speed increase from 40 to value of for smooth boiler start Fan work time n 5 time of turning the fan on for a while to remove...

Страница 8: ...ion Central heating pump turn off delay Pd 2 central heating pump stopping too early can cause temperature rise in the boiler and cause its overheating This parameter allows setting central heating pu...

Страница 9: ...described above When contacts are open the controller will keep minimum boiler temperature Attention When external thermostat is connected in place of room temperature sensor the temperature set with...

Страница 10: ...ing boiler start Fuel shortage testing time in work mode Fb30 time set with this parameter is used when testing fuel shortage after boiler has started Setting this parameter to disables fuel shortage...

Страница 11: ...are working correctly After detection of fault it stops the pressure fan turns on the circulating pump and shows proper error message on the display In case of failure please turn off the controller p...

Страница 12: ...urement range 9 109 C 1 C Boiler temperature adjustment range 30 90 C 1 C Programmable boiler overheating protection 90 99 C 1 C Hardware boiler overheating protection 95 C 1 C Circulating pump launch...

Страница 13: ...13 Picture 2 RK 2001AT2 connection scheme Picture 3 UM 1 module connection scheme...

Страница 14: ...controller work mode Pc Central heating pump pause time Pd 2 Central heating pump turn off delay L 65 Minimum boiler temperature H 90 Maximum boiler temperature h 5 Boiler temperature hysteresis A105...

Страница 15: ......

Страница 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Отзывы: