background image

Product history:

Date

Version

Changes

2010-08-03 A803

Exhaust gas thermostat is used solely for „no fuel” detection.

2010-09-13 A913

Exhaust gas temperature drop below value set with

thermostat knob will stop the fan and central heating pump.

This will not work if boiler temperature is below minimum

temperature.

2010-12-10 AC10

After pressing STOP, START again the controller starts in

HEATING UP mode. This mode turns off influence of exhaust

gas thermostat on the fan and central heating pump.

HEATING UP is active until exhaust gas temperature achieves

temperature set with thermostat knob. Protection against too

high exhaust gas temperature has been added.

2010-12-20 AC20

In FC1 mode central heating pump is turned off after FUEL

alarm.

2010-12-22 AC22

If boiler temperature is less than set temperature and is within

hysteresis, then after pressing STOP, START again the

controller starts in WORK mode (it was SUSTAIN mode in

previous versions).

Содержание RK-2001AT2

Страница 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001AT2 Version AC22...

Страница 2: ...r starts in HEATING UP mode This mode turns off influence of exhaust gas thermostat on the fan and central heating pump HEATING UP is active until exhaust gas temperature achieves temperature set with...

Страница 3: ...shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if the screws of the connector are properly screwed CA...

Страница 4: ...on stops the fan for example allowing to add fuel to the boiler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode...

Страница 5: ...splays current measured room or exhaust gas temperature 6 Setting up the parameters service mode Holding OK button for more than 3 seconds causes change to service mode where you can view and change p...

Страница 6: ...ng pump turn off delay 1 99 1min 2 L 65 Minimum boiler temperature 60 65 1 C 65 H 90 Maximum boiler temperature 80 95 1 C 90 h 5 Boiler temperature hysteresis 1 10 1 C 5 A105 Boiler overheating temper...

Страница 7: ...meter value in range from 0 to 10 means time in minutes of the smooth fan speed increase from 40 to value of for smooth boiler start Fan work time n 5 time of turning the fan on for a while to remove...

Страница 8: ...ion Central heating pump turn off delay Pd 2 central heating pump stopping too early can cause temperature rise in the boiler and cause its overheating This parameter allows setting central heating pu...

Страница 9: ...described above When contacts are open the controller will keep minimum boiler temperature Attention When external thermostat is connected in place of room temperature sensor the temperature set with...

Страница 10: ...ing boiler start Fuel shortage testing time in work mode Fb30 time set with this parameter is used when testing fuel shortage after boiler has started Setting this parameter to disables fuel shortage...

Страница 11: ...are working correctly After detection of fault it stops the pressure fan turns on the circulating pump and shows proper error message on the display In case of failure please turn off the controller p...

Страница 12: ...urement range 9 109 C 1 C Boiler temperature adjustment range 30 90 C 1 C Programmable boiler overheating protection 90 99 C 1 C Hardware boiler overheating protection 95 C 1 C Circulating pump launch...

Страница 13: ...13 Picture 2 RK 2001AT2 connection scheme Picture 3 UM 1 module connection scheme...

Страница 14: ...controller work mode Pc Central heating pump pause time Pd 2 Central heating pump turn off delay L 65 Minimum boiler temperature H 90 Maximum boiler temperature h 5 Boiler temperature hysteresis A105...

Страница 15: ......

Страница 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...