STB

- the controller has also additional protection from overheating, which is

independent from the processor, . In case of temperature increase over 95°C, the

control process is turned off by turning the fan off and launching the circulating pump.

The fan and the pump are joined to the control process again, when temperature

reaches 89°C. STB circuit enables more precise boiler work control and reduces

overheating possibility.

6.5. Additional thermostat work mode.

Additional thermostat work mode [Fc 1]

- the controller is equipped with additional

thermostat and temperature sensor connection. This parameter selects work mode of

the additional thermostat and additional sensor connection.

- mode

[Fc 0]

- means that room temperature sensor is connected to the

additional sensor connection. RK-2001AT2 will compare measured room temperature

with temperature set with additional thermostat knob. When room temperature is lower

than the desired temperature, room thermostat indicator will be lit meaning that boiler

should keep temperature set with boiler thermostat knob. When room temperature

reaches desired temperature, room thermostat indicator will be switched off and boiler

enters fire keeping mode at minimum boiler temperature. Device design allows for

connecting any external contact thermostat in place of room temperature sensor.

Shorting the contacts when temperature is low will start the heating procedure

described above. When contacts are open, the controller will keep minimum boiler

temperature.

Attention!

When external thermostat is connected in place of room

temperature sensor, the temperature set with room thermostat knob on the device will

not affect the controlling process and room temperature will depend solely on

temperature set on external contact thermostat.

- mode

[Fc 1]

- means that exhaust gas temperature sensor is connected to the

additional sensor connection. In this case the value set with additional thermostat knob

specifies desired exhaust gas temperature. If the controller is in WORK mode and

boiler water temperature has reached value set with [P 65] parameter, then exhaust

gas temperature drop below temperature set with additional thermostat knob will stop

the fan. If central heating pump is in [Pr 1] mode, the pump will also stop in this case.

Additionally, if exhaust gas temperature is below desired temperature, this will also be

signaled with quick blinking of thermostat indicator.

6.6. High exhaust gas temperature protection .

If exhaust gas temperature sensor is connected to additional input ([Fc 1]), the

controller can protect from too high exhaust gas temperature. Next two parameters

control this function.

Maximum exhaust gas temperature [F300]

– this parameter controls maximum

temperature which exhaust gas is allowed to achieve. If exhaust gas temperature is

higher than programmed value, the controller displays [Hot ] and turns off the fan.

Normal work resumes after the temperature drops by value of hysteresis. Setting this

parameter to „---” turns off high exhaust gas temperature protection.

Содержание RK-2001AT2

Страница 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001AT2 Version AC22...

Страница 2: ...r starts in HEATING UP mode This mode turns off influence of exhaust gas thermostat on the fan and central heating pump HEATING UP is active until exhaust gas temperature achieves temperature set with...

Страница 3: ...shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if the screws of the connector are properly screwed CA...

Страница 4: ...on stops the fan for example allowing to add fuel to the boiler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode...

Страница 5: ...splays current measured room or exhaust gas temperature 6 Setting up the parameters service mode Holding OK button for more than 3 seconds causes change to service mode where you can view and change p...

Страница 6: ...ng pump turn off delay 1 99 1min 2 L 65 Minimum boiler temperature 60 65 1 C 65 H 90 Maximum boiler temperature 80 95 1 C 90 h 5 Boiler temperature hysteresis 1 10 1 C 5 A105 Boiler overheating temper...

Страница 7: ...meter value in range from 0 to 10 means time in minutes of the smooth fan speed increase from 40 to value of for smooth boiler start Fan work time n 5 time of turning the fan on for a while to remove...

Страница 8: ...ion Central heating pump turn off delay Pd 2 central heating pump stopping too early can cause temperature rise in the boiler and cause its overheating This parameter allows setting central heating pu...

Страница 9: ...described above When contacts are open the controller will keep minimum boiler temperature Attention When external thermostat is connected in place of room temperature sensor the temperature set with...

Страница 10: ...ing boiler start Fuel shortage testing time in work mode Fb30 time set with this parameter is used when testing fuel shortage after boiler has started Setting this parameter to disables fuel shortage...

Страница 11: ...are working correctly After detection of fault it stops the pressure fan turns on the circulating pump and shows proper error message on the display In case of failure please turn off the controller p...

Страница 12: ...urement range 9 109 C 1 C Boiler temperature adjustment range 30 90 C 1 C Programmable boiler overheating protection 90 99 C 1 C Hardware boiler overheating protection 95 C 1 C Circulating pump launch...

Страница 13: ...13 Picture 2 RK 2001AT2 connection scheme Picture 3 UM 1 module connection scheme...

Страница 14: ...controller work mode Pc Central heating pump pause time Pd 2 Central heating pump turn off delay L 65 Minimum boiler temperature H 90 Maximum boiler temperature h 5 Boiler temperature hysteresis A105...

Страница 15: ......

Страница 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Отзывы: