manualshive.com logo in svg
background image

 

IL05003012E.pdf 

                                         

5011630506-C206

2007-05-08

 

ELC-PC12NNDR/T

 

ELC-PC12NNAR 

Logic Controller with Multi-Function, 
Multiple Commands

 

Instruction Sheet

 

 

WARNING 

 

This Instruction Sheet only provides descriptions for electrical specifications, general specifications, 
installation & wiring, troubleshooting and peripherals. Other detail infromation about programming and 
commands is compatible with ELC-PC/PA/PH series; please see ELC Application Manual. For more 
information about the optional peripherals , please see individual product manual. 

 

This is an OPEN TYPE Controller. The ELC should be kept in an enclosure away from airborne dust, humidity, 
electric shock risk and vibration. Also, it is equipped with protective methods such as some special tools or 
keys to open the enclosure, so as to avoid the hazard to users and the damage to the ELC. 

 

Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the 
ELC.    Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the ELC is 
properly grounded 

. Do NOT touch terminals when power on. 

 

Battery replacement: use UL component type: TDRTL-2150/S lithium battery. Refer to following table for 
battery life. (NOTE: RTC should be reset after changing battery). 

Temperature((

°

C) 

0  25 50 70 

Life(Years) 

9 8 6 5 

Precision of calendar timer: 

At 0

°

C/32

°

F, less than –117 seconds error per month. 

At 25

°

C/77

°

F, less than 52 seconds error per month. 

At 55

°

C/131

°

F, less than –132 seconds error per month. 

 

Warning – Do not disconnect while circuit is live unless area is known to be non-hazardous. 

 

Power, input and output (I/O) wiring must be in accordance with Class 1, Div. 2 wiring methods - Article 
501-10(B)(1) of the National Electrical Code. 

 

Suitable for use in Class 1, Division 2, Groups A, B, C, D or Non-Hazardous locations only. 

 

Warning – Explosion hazard - Substitution of components may impair suitability for Class 1, Division 2. 

 

Warning – Wxplosion hazard - Do not disconnect equipment unless power has been switched off or the area 
is known to be Non-Hazardous. 

 

1  

INTRODUCTION 

1.1  Model Name Explanation and Peripherals 

Thank you for choosing Eaton Logic Controller (ELC) series products. The ELC-PC series has a 12-points (8 input 

 4 outputs) ELC main processing unit with multiple commands for use. It also has an 8K Steps program 

memory to connect to every ELC-PC series expansion unit, including digital I/O (Maximum 128 Inpus / 128 Outputs 

expansion points), analog module, etc. for various applications. 

 

1.2  Product Profile and Outline 

E

L

C

-P

C

12N

N

A

R

Y3

RS

-2

32

RS

-4

85

Y1

Y2

C2

Y0

C1

RUN

RUN

ERROR

POWER

 

Unit: mm 

Warning: Battery replacement: Please change the battery within 3 

minutes, or the internal data of the ELC (including the program area, 

perpetual calendar and latched registers) could be lost or destroyed. 

1  Status indicator: POWER, RUN, 

ERROR, BAT.LOW 

2  RUN/STOP switch 
3  VR0: M1178 Start-up/D1178 

Corresponding value 

4  VR1: M1179 Start-up/D1179 

corresponding value 

5  DIN rail clip 
6  I/O terminals 
7  I/O point indicators 
8  COM1 (RS-232) (Rx) indicator 
9  COM2 (RS-485) (Tx) indicator 

10  COM1 (RS-232) programming port 

11  Nameplate 

12  Expansion port 
13  Mounting hold of the expansion unit 

 

14 DIN rail (35mm) 
15 Expansion unit clip 
16 COM2 (RS-485) Communication port 
17 DC Power input 
18 2 pin removable terminal (standard 

accessory) 

19 Power input cable (standard 

accessory) 

20 Battery Cover 
21 Battery socket connection 
22 Battery mount 

 

2  

FUNCTION SPECIFICATIONS 

 

Items 

Specifications 

Remarks 

Control Method 

Stored program, cyclic scan system 

 

I/O Processing Method 

Batch processing method (when END command 
is executed) 

I/O refresh command is 
available 

Execution Speed 

Basic commands (several us) 

Application Commands 
(10~hundreds us) 

Program Language 

Co Ladder Logic + SFC 

Including the Step commands 

Program Capacity 

7,920 STEPS 

SRAM + Battery 

Commands 

32 Basic sequential commands 168 

Application 

commands 

Rela

y (bit 

mode)

 

X  External Input Relay 

X0~X177, octal number system, 128 
points 

Total 

256 

points

Correspond to external I/P 
point 

Y  External Output Relay 

Y0~Y177, octal number system, 128 
points 

Correspond to external O/P 
point 

Auxiliary 

Relay 

General 

M0~M511, 512 points (*1) 

Total 

4,096 

points

Contacts can switch to On/Off 
in program 

Latched 

M512~M999, 488 points (*3) 
M2000~M4095, 2,096 points (*3) 

Special 

M1000~M1999, 1,000 points (some are 
latched) 

T Timer 

100ms 

T0~T199, 200 points (*1) 

Total 

256 

points

When the timer that set by 
TMR command reaches the 
preset value, the T contact with 
the same number will be On. 

T192~T199 for Subroutine 
T250~T255, 6 points Accumulative (*4) 

10ms 

T200~T239, 40 points (*1) 
T240~T245, 6 points Accumulative (*4) 

1ms 

T246~T249, 4 points Accumulative (*4) 

C Counter 

16-bit Count 
Up 

C0~C95, 96 points (*1) 

Total 

250 

points

When the counter that set by 
CNT (DCNT) command 
reaches the preset value, the C
contact with the same number 
will be On. 

C96~C199, 104 points (*3) 

32-bit Count 
Up/Dn 

C200~C215, 16 points (*1) 
C216~C234, 19 points (*3) 

32bit 
High-speed 
Count Up/Dn 

C235~C245, 1 ph, 1 input, 9 points (*3) 
C246~C250, 1 ph, 2 input, 3 points (*3) 
C251~C254, 2 ph, 2 input, 3 points (*3) 

Step 
point 

Initial Step 
Point 

S0~S9, 10 points (*1) 

Total 

1,024 

points

Usage device of step ladder 
diagram (SFC) 
Latched Range: 
Start: D1214 (K512) 
End: D1215 (K895)   

Zero Point 
Reset 

S10~S19, 10 points (use with IST 
command) (*1) 

General 

S20~S511, 492 points (*1) 

Latched 

S512~S895, 384 points (*3) 

Alarm 

S896~S1023, 128 points (*3) 

Regi

ster (W

ORD d

at

a)

 

Current Value of the 
Timer 

T0~T255, 256 points 

When the timer reaches the 
preset value, the contact of 
timer will be On. 

Current Value of the 
Counter 

C0~C199, 16-bit counter, 200 points 
C200~C254, 32-bit counter, 50 points 

When the counter reaches the 
preset value, the contact of 
counter will be On. 

Data 
Register 

General 

D0~D199, 200 points (*1) 

Total 

5,000 

points

Can be memory area for 
storing data.    E and F can be 
used as the special purpose of 
index indication. 

Latched 

D200~D999, 800 points (*3) 
D2000~D4999, 3,000 points (*3) 

Special 

D1000~D1999, 1,000 points 

Index 

E0~E3, F0~F3, 8 points (*1) 

None

File Register 

0~1,599 (1,600 points) (*4) 

Expansion register for storing 
data. 

Pointer

 

For Master Control 
Nested Loop 

N0~N7, 8 points 

Control point of master control 
nested loop 

For CJ, CALL 
Commands 

P0~P255, 256 points 

The location point of CJ, CALL.

Inte

rrup

t Se

rvi

ce

 

External Interrupt

I001 (X0), I101 (X1), I201 (X2), I301 (X3), I401 
(X4), I501 (X5); 6 points (all are rising-edge 
trigger) 

The location pointer of interrupt 
subroutine 

Time Interrupt 

I6

 (1ms), I7

 (1ms), (

1~99ms) 

*1: The non-latched area is fixed, and can’t be changed.   

*2: The non-latched area can be changed to a latched area with parameter setting. 

*3: The latched area can be changed to a non-latched area with parameter setting. 

*4: The latched area is fixed, and can’t be changed. 

Auxiliary 

Relay 

General 

Latched 

Special auxiliary relay 

Latched 

M0~M511 M512~M999 

M1000~M1999 M2000~M4095 

Non-latched (fixed) 

Latched (default) 

Some are latched and 

can’t be changed 

Latched (default) 

Start: D1200 (K512)   

End: D1201 (K999)   

Start: D1202 (K2,000) 

End: D1203 (K4,095) 

Timer 

100 ms 

10 ms 

10ms 

1 ms 

100 ms 

T0 ~T199 

T200~T239 

T240~T245 T246~T249 T250~T255 

Non-latched (fixed) 

Non-latched (fixed) 

Accumulative Latched (fixed) 

Counter 

16-bit count up 

32-bit count up/down 

32-bit high-speed count up/down

C0~C95 C96~C199 

C200~C215

C216~C234 C235~C245 

C246~C255

Non-latched 

(fixed) 

Latched (default) 

Non-latched 

(fixed) 

Latched (default) 

Latched (default) 

Start: D1208 (K96)   
End: D1209 (K199) 

Start: D1210 

(K216)  

End: D1211 (K234) 

□□

□□

□□=

Hi-speed Counter  I010, I020, I030, I040, I050, I060; 6 points 
Communication 

I150, 1 point 

C

ons

ta

nt 

K Decimal 

K-32,768 ~ K32,767 (16-bit operation) 
K-2,147,483,648 ~ K2,147,483,647 (32-bit operation) 

H  Hexadecimal 

H0000 ~ HFFFF (16-bit operation), H00000000 ~ HFFFFFFFF (32-bit operation) 

Programming Port 

COM1: RS-232, COM2: RS-485 (Master/Slave), Can be used at the same time. 

Analog Volume / Perpetual 
Calendar (RTC) 

ELC built-in 2 points VR / ELC built-in RTC 

Special Expansion Module 

Use the same modules of ELC series. (Max. 8 Expansion Unit points) 

Start: D1212 (K235)   

End: D1213 (K255)   

Step Relay

For general  Latched  Special register 

Latched 

For general 

S0~S9 S10~S19  S20~S511 

S512~S895 

S896~S1023 

It is fixed to be non-latched 

Factory setting is latched 

It is fixed to be latched 

Start: D1214 K512  

End: D1215 K895  

Register 

General 

Latched Special 

registers Latched 

D0~D199 D200~D999 

D1000~D1999 D2000~D4999 

Non-latched (fixed) 

Factory setting is 

latched. 

Some are latched and 

can’t be changed. 

Factory setting is 

latched. 

Start: D1216 (K200)   

End: D1217 (K999)   

Start: D1218 (K2,000) 

End: D1219 (K4,999) 

File 

Register 

K0~K1,599 

Latched (fixed) 

When switching between power On/Off or ELC RUN/STOP modes: 

Memory Type 

POWER 

Off

Ö

On 

STOP

Ö

RUN 

RUN

Ö

STOP 

Clear all M1031 

non-latched area

Clear all M1032 

latched area 

Factory 

Setting

Non-latched Clear 

Unchanged 

M1033=Off, clear 

Clear Unchanged 

M1033=On, 

unchanged 

Latched Unchanged 

Unchanged 

Clear 

Special M, Special 

D, Index register  Initial value 

Unchanged 

Unchanged 

Initial 
value 

File register 

Unchanged 

 

3

ELECTRICAL SPECIFICATIONS 

 

                                      Model   
  Item 

ELC-PC12NNDR/T 

ELC-PC12NNAR 

Power Supply Voltage 

ELC: 24VDC (-15%~+20%) (With DC input reverse polarity protection),   
Expansion Unit: supplied by the ELC 

Fuse 

2A / 250VAC 

Power Consumption 

3.5W MAX 

Insulation Resistance 

> 5 M   at 500 VDC (Between all inputs / outputs and earth) 

Ω

Noise Immunity 

ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, Analog & 
Communication I/O: 1KV 
RS(IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m 

Grounding 

The diameter of grounding wire cannot be smaller than the wire diameter of 
terminals 24V and 0V (All ELC units should be grounded directly to the ground 
pole). 

Environment 

Operation: 0 ~55   (Temperature), 50~95% (Humidity), Pollution degree 2;   

Storage: -25 ~70  (Temperature), 5~95% (Humidity) 

Agency Approvals 

UL508 
UL1604, Class1,Div2  Operating temperature code: T5 
European community EMC Directive 89/336/EEC and Low Voltage Directive 
73/23/EEC 

Vibration / Shock Resistance 

Standard: IEC61131-2, IEC 68-2-6 (TEST Fc) / IEC61131-2 & IEC 68-2-27 (TEST 
Ea) 

Weight (approx.) (g) 

158 

 

DC Input Point Electrical Specification 

Input Type 

DC (SINK or SOURCE) 

Input Current 

24VDC 5mA 

Active Level 

Off On 

X0,X1: above18.5VDC 

On Off 

X0~X7: below 8VDC 

X2~X7: above16.5VDC 

Отзывы: