ESC - press to return to the previous display
Info button - gives operating instructions
Browse button - moves the cursor up and down
ESC
Group select button - not in use in EH201/L
15
OUMAN EH-203
OUMAN EH-203
OUMAN EH-201/L
OUMAN EH-201/L
Press the
button to move cursor to "Clock functions”. Press
OK.
Clock functions; relay control
Clock functions
Time/ Date
H1 drop program
R1 Time program
R2 Control
Press the
button to move cursor to indicate the relay control (R1 or
R2) whose controls you want to access. Press
OK.
0:00 Relay1ON
_ _ _ _ _
_ _
0:00 RelayOFF
_ _ _ _ _ _ _
H1 Select
Heating curve
Settings
Measurements
Info water temp
Control
modes
Clock functions
Language/Keel
Press
ESC
until the display no longer changes.
You are then in the "Selection" display shown in the adjoining picture.
OPERATING INSTRUCTION:
Press
OK.
H1
Outdoor
°C
SupplyTemp
°C
Selection
Automatic
-15
52
R1 Control
Time program
Contin ON
Contin OFF
Timer ON
m
Timer OFF
m
0
0
The relay can be used to switch an electric apparatus on and off at desired
times. When the time program is in the "ON” mode the relay is activated. In
this mode the time (time and weekday) is set for the relay to be activated
and the time (time and weekday ) is set for the relay to be inactivated. Time
programming is done in the same way as L1 drop program time
programming (see prev. p.). The regulator can be programmed for a
maximum of 7 program series (on/off series) per relay.
The relay's time program is not in use. The relay is in a forced ON mode
(= relay is activated).
The relay is in a forced Off mode (= relay is inactivated).
The relay's time program is temporarily replaced by a timer. The relay is in
the ON mode (= activated) for a set time (range 0…999min), after which the
relay switches to a time programmed mode. Press the or + button to change
the time on the timer. The amount of time left on the timer appears on the
display.
The relay's time program is temporarily replaced by a timer. The relay is in
the OFF mode (= is inactivated) for a set time (range 0…999min), after which
the relay switches to a time programmed mode. Press the or + button to
change the time on the timer. The amount of time left on the timer appears
on the display.
Time program:
Continuous ON:
Continuous OFF
Timer ON
Timer OFF
Set the time for the relay to be activated and the
days of the week for the relay to be activated.
In addition, set the time for the relay to be inactivated
and the days of the week for the relay to be inactivated.
Press the
or
button and confirm the time on the timer by pressing
.
-
+
OK
If the relay reserved for time control has been labeled, R1 (R2) it will
indicate what the relay is reserved for (e.g., sauna, outside doors)
RELA
Y1:
(T
ime
program/
ON/OFF/
Timer
ON
min/
Timern
OFF=
min)
59
*
59
RELA
YS
KEYWORD:
Relays
Relays can control many different functions, e.g., sauna stoves, locking
doors etc. Relay clock functions are taken into use and labeled according
to use in the relay control mode. (see p. 26 - 28). Then the relay can be
controlled using a GSM, if a GSM has been installed into the regulator
(optional equipment).