Measurement information:
Strip
con-
nector
OUMAN EH-203
MITTAUKSET
OUMAN EH-203
OUMAN EH-201/L
MEASUREMENTS
OUMAN EH-201/L
Additional information
Putting sensor into use and removing it from use:
Resistance
value table
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
90
100
110
177 100
130 400
96 890
72 830
55 340
42 340
32 660
25 400
19 900
15 710
12 490
10 000
8 064
6 531
5 330
4 368
3 602
2 987
2 490
2 084
1 753
1 482
1 259
917
680
511
Measure-
ment:
Attention!
°C
INSTRUCTIONS FOR CONNECTING SENSORS:
TMR
Free temp.measurement
(Measurement 11)
2 x 0.8
2 x 0.8
2 x 0.8
2 x 0.8
TMW or TMS
TMW or TMS
TMW or TMS
TMW or TMS
Meas.3
Meas.4
Meas.9
Meas.10
Meas.11
Meas.1
TMO
TMW or TMS
2 x 0.8
2 x 0.8
2 x 0.8
Meas.2
Outdoor temp. sensor
H1 Supply water sensor
H1 Room sensor
Free temp.measurement
H1 Return water sensor
Free temp. measurement
(Measurement 9)
Free temp. measurement
(Measurement 10)
1
2
Supply
3
3
Wind
3
Sun
(m )
Inst. l/s
Actuator
Actuator
4
Return
9
Meas. 9
10
Meas. 10
11
Meas. 11
Out temp
H1 Supply
H1 Room
H1 Ret.water
DH m3
DH MWh
Inst. KW
Wat m3
H1
Outdoor temperature
water temperature in regulating circuit H1
Room temp. in regulating circuit H1
Wind speed (% of sensor's range)
Amount of light (% of sensor's range)
3
Meas. 3
Free measurement, information type measure-
ment which can be relabeled through text editing.
water temperature in regulating circuit H1
Free measurement; name using the text editor
Free measurement; name using the text editor
Free measurement; name using the text editor
Measured consumption of DH water
Measured energy consump. of DH water (MWh)
DH energy consumption in kW (5 min. period)
Measured water consumption of facility (m )
position in regulating circuit H1
(room comp.)
3
3
Momentary district heating water consumption (l/s)
Setting
range:
-50...+50
0 . . . + 1 3 0
0 . . . + 6 0
0 . . . + 1 3 0
0 . . . + 1 3 0
.
0 . . . + 1 3 0
0 . . . + 1 3 0
0...+120
0...9999999.9
0...99999.9
0...3276.7
0...99999.9
Interchangeable (p. 29). If
several compensations are
needed, the data must be
read through the net and the
wind is m/s and the light is
lux (p. 34).
Can be read through the net
Measurement data through
a digital input or the net.
Appears only when using a
0...10V (2...10V) controlled
If the outdoor sensor is not connected, the regulator assumes that the outdoor temperature is
0°C and a sensor fault message appears on the display (Outdoor temp err). When the outdoor
sensor is connected, the regulator automatically takes it into use.
(See page 18)
After adding other sensors
you must go to start function!
2
3
4
9
10
11
1
TMR
T1
T2
T3
T4
T9
T10
T1
1
ESC - press to return to the previous display
Info button - gives operating instructions
Browse button - moves the cursor up and down
ESC
Group select button - not in use in EH201/L
10