PC-250 Filter control unit operating manual   Page: 11 (24 

The  floating  relay  contact  between  terminals  22  and  23  can  be  loaded  with  a  voltage  of 
maximum 230 V and a current of maximum 8 A. 

If  the  heater  requires  230  V,  it  can  be  connected  to  terminal  U2.  Terminals  are  also 
available for the heater N connection. 

A 230 V 

 solar actuating drive can be connected to terminals U5 and U6 for operating 

the  solar  heater.  When  operating  solar  heater,  terminal  U5  carries  the  mains  voltage  and 
terminal  U6  is  voltage-free.  If  the  solar  heater  is not  being operated,  terminal U5  remains 
voltage-free  and  terminal  U6  carries  the  mains  voltage.  These  contacts  may  the  loaded 
with a maximum 230 V/1.5A.  

Level regulation and backflushing control 

Filtersteuerung PC-30

NR-12-TRS-2

steuerung

Auffangbehälter-

11 12 13 14

11 12 13 14

U3 N

R

ü

c

ks

p

ü

lv

e

n

ti

l

230V

m

a

x

.2

A

EUROTRONIK-10

2 3 4 5

2 3 4 5

Rückspülsteuerung

U4 N

K

la

rs

p

ü

lv

e

n

ti

l

230V

m

a

x

.2

A

 

A 230 V bar valve for backflushing can be connected to terminals U3 and N.  

A 230 V bar valve for rinsing can be connected to terminals U4 and N. 

Both valves will be controlled by the internal backflushing controller. 

Heater and dosing systems are blocked during the backflushing and rinsing processes. 

Either bar valves or a EUROTRONIK-10 can be used for backflushing or rinsing. 

The  bridge  fitted  in  the  works  between  terminals 

13

  and 

14

  must  be  removed  if  level 

regulation  system  NR-12-TRS-2  is  connected.  The  bridge  can  remain  between  these 
terminals if no level regulation system is connected. Terminals 

11

 and 

12

 remain unused in 

this case. These terminals carry mains voltage! 

The  bridge  fitted  in  the  works  between  terminals 

3

  and 

5

  must  be  removed  if  a 

EUROTRONIK-10 system is connected. The bridge can remain between these terminals if 
no EUROTRONIK-10 system is connected. Terminals 

2

 and 

4

 remain unused in this case. 

These terminals carry mains voltage! 

Opening any of the contacts  between terminals 

13 

and 

14 

or 

and 

causes filter pump, 

dosing systems and heater to be turned off immediately. 

Closing  any  of  the  contacts  between  terminals  2  and  4  or  11  and  12  causes  forced 
switching on of the filter pump, whereas heater and dosing systems are switched off. 

Содержание POOL-Control-250

Страница 1: ...pecifications Dimensions 220mm x 220mm x 100mm Operational voltage 400V 50Hz Control system power consumption ca 10VA Switching capacity Pump max 3 0 kW AC3 Heater max 2A Dosing system max 8A Protecti...

Страница 2: ...ng switching times 8 Start backflushing process manually 8 Info key 8 Installation 9 Electrical power supply 9 Mains connection when using 400V 3 phase pump 10 Mains connection when using 230 V AC pum...

Страница 3: ...n on time 17 Heater priority circuit 18 Solar heater priority circuit 18 Frost protection 19 Pump time 19 heater time 19 Solar time 19 Motor defect 19 Phase fields 19 Int backflushing intern 19 Ext Ba...

Страница 4: ...y This controller is not usable for other types of solar collector Terminals for electronic level regulation NR 12 TRS 2 Art No 3030075020 enable convenient automatic regulation of the swimming pool w...

Страница 5: ...R ck sp len The filter pump is switched on because backflushing is taking place using the bar valve connected Klar sp len The filter pump is switched on because rinsing is taking place using the bar v...

Страница 6: ...he control system this indicator lamp is used to show the current operating status of the solar heater Backflushing process indicator lamp This indicator lamp always illuminates if backflushing or rin...

Страница 7: ...y shows 0 00 0 00 1 the minute display of the top time switch on time blinks Note if you press the key the current time will be taken over 3 You can now use the and keys to set the required switch on...

Страница 8: ...et the minutes If you press the key the current time is taken over 4 Press the key again the hours in the switch on time blink You can now use the and keys to set the hours 5 Press the key again the s...

Страница 9: ...display automatically Installation The controller must be protected against moisture in accordance with its protection class and the fixed to a plain fireproof support with suitable loading capacity...

Страница 10: ...L1 N WSK schutz 230V max 8A Filterpumpe max B16A Vorsicherung FI Schalter Netz 1 N 230V 50Hz 25A 0 03A N kontakt The bridge fitted in the works between the terminals labelled WSK must be removed if a...

Страница 11: ...N A 230 V bar valve for rinsing can be connected to terminals U4 and N Both valves will be controlled by the internal backflushing controller Heater and dosing systems are blocked during the backflus...

Страница 12: ...h good heat transfer between temperature sensor and swimming pool water an immersed sleeve R Art No 3200200003 should be built into the piping system The sensor polarity is as required A solar tempera...

Страница 13: ...e right Fuses The electronic control system is protected by a 0 25A fine wire fuse on the PCB in the inside of the device The short circuit protection for the filter pump must be provided by a backup...

Страница 14: ...tched off temporarily by the EUROTRONIK 10 or the NR 12 TRS 2 level regulation system Backflushing The filter pump is switched on because backflushing is taking place using the bar valve Rinsing The f...

Страница 15: ...defective Caution If both temperature sensors are at the same temperature the solar sensor must never display a higher value than the water temperature sensor otherwise the solar heater will not swit...

Страница 16: ...e value is 0 the largest 15 3 If you press the key again the normal diagnosis display appears and the filter unit continues to operate The adjusted value will be saved automatically A temperature diff...

Страница 17: ...d the filter unit is switched off and the display shows the following Min Solar s Minimale Einschaltzeit der Solarheizung 120 2 Use the and keys to change the minimum time in stages of 10s The smalles...

Страница 18: ...3 If you press the key again the normal diagnosis display appears and the filter unit continues to operate The additional heater priority is switched off at the works Solar heater priority circuit Thi...

Страница 19: ...ump time This line displays the total operating hours for the filter pump heater time This line displays the total operating hours for the additional heater Solar time This line displays the total ope...

Страница 20: ...he filter pump operating status is displayed in the top line of the service terminal the pump can be switched on or off manually 1 Once the key has been pressed the filter unit is switched off and the...

Страница 21: ...tinues to operate Dosing unit When the dosing unit operating status is displayed in the top line of the service terminal it can be switched on or off manually 1 Once the key has been pressed the filte...

Страница 22: ...ormal diagnosis display appears and the filter unit continues to operate Diagnosis This menu is only accessible for trained osf service technicians Language When the language is shown in the top line...

Страница 23: ...ungsschutz Filterpumpe Temperaturf hler Heizungspumpe W Netz 400V Dosiertechnik Dosier pumpe N Netz 230V 1 N PE Ausgang Pumpe Druckschalter Netz 230V 1 N PE Stellantrieb Ge ffnet bei R cksp len und Kl...

Страница 24: ...PC 250 Filter control unit operating manual Page 24 24...

Отзывы: