IG-267-EN versión 01; 07/04/2017
75
General Instructions
ekor
.rpa
User configuration settings
Continuation
Type Class
Node
Settings
Type
Designation
Range
Min.
Max.
Step (unit)
Curr
en
t pr
ot
ec
tion
(CURRENT_PR
O
TEC
TION)
O
ver
curr
en
t pr
ot
ec
tion
(O
VER
CURRENT
)
Sensitive
neutral timed
unit (1)
(UNIT_51NS)
Enabling the unit
Enable
ON/OFF
Starting up the unit
Pick_up*
(with vector sum)
0.5
1.5
1.5
1500.0
5000.0
5000.0
0.1 (A)
0.1 (A)
0.1 (A)
Pick_up*
(with zero-sequence
toroidal)
0.3
0.3
0.3
1500.0
5000.0
5000.0
0.1 (A)
0.1 (A)
0.1 (A)
Time curve
Curve
IEC: DT, NI, VI, EI, STI and LTI
ANSI: NI, VI, EI and LI
Inverse curve time index
Index
0.05
1.60
0.01
Fixed time
Time
0.00
100.00
0.01 (s)
Torque control
Direction
OFF/FORWARD/REVERSE
Sensitive
neutral timed
unit (2)
(UNIT_51_2_
NS)
Enabling the unit
Enable
ON/OFF
Starting up the unit
Pick_up*
(with vector sum)
0.5
1.5
3.7
1500.0
5000.0
12,500.0
0.1 (A)
0.1 (A)
0.1 (A)
Pick_up*
(with zero-sequence
toroidal)
0.3
0.3
0.3
1500.0
5000.0
5000.0
0.1 (A)
0.1 (A)
0.1 (A)
Time curve
Curve
IEC: DT, NI, VI, EI, STI and LTI
ANSI: NI, VI, EI and LI
Inverse curve time index
Index
0.05
1.60
0.01
Fixed time
Time
0.00
100.00
0.01 (s)
Torque control
Direction
OFF/FORWARD/REVERSE
Sensitive
neutral
instantaneous
unit
(UNIT_50NS)
Enabling the unit
Enable
ON/OFF
Starting up the unit
Pick_up*
(with vector sum)
0.5
1.5
3.7
1500.0
5000.0
12,500.0
0.1 (A)
0.1 (A)
0.1 (A)
Pick_up*
(with zero-sequence
toroidal)
0.3
0.3
0.3
1500.0
5000.0
5000.0
0.1 (A)
0.1 (A)
0.1 (A)
Unit timing
Time
0.00
100.00
0.01 (s)
Torque control
Direction
OFF/FORWARD/REVERSE
D
ir
ec
tional units
(DIREC
TIONAL)
Phase
directional unit
(UNIT_67)
Characteristic phase angle
Characteristic
Angle
90.0
90.0
0.1 (º)
Minimum phases voltage
V_min
0.5
72.0
0.1 (kV)
Indeterminate zone
Indeterminate_zone
0.0
90.0
0.1 (º)
Neutral
directional unit
(UNIT_67N)
Directional method type
Type
ANG/WAT
Characteristic neutral angle
Characteristic
Angle
-90.0
90.0
0.1 (º)
Minimum neutral active power
P_min
2.5
15 000.0
0.1 (kW)
Minimum neutral voltage
V_min
0.5
72.0
0.1 (kV)
Indeterminate zone
Indeterminate_zone
0.0
90.0
0.1 (º)
Sensitive
neutral
directional unit
(UNIT_67NS)
Directional method type
Type
ANG/WAT
Characteristic sensitive neutral angle
Characteristic
Angle
-90.0
90.0
0.1 (º)
Minimum neutral active power
P_min
2.5
15,000.0
0.1 (kW)
Minimum neutral voltage
V_min
0.5
72.0
0.1 (kV)
Indeterminate zone
Indeterminate_zone
0.0
90.0
0.1 (º)
Continued on next page