Protection functions
General Instructions
ekor
.rpa
The second harmonic blocking unit generates the following
signal:
•
UHARM_IA_BLOCK
: Signal which indicates whether
phase A complies with the conditions necessary for
second harmonic blocking or not.
•
UHARM_IB_BLOCK
: Signal which indicates whether
phase B complies with the conditions necessary for
second harmonic blocking or not.
•
UHARM_IC_BLOCK
: Signal which indicates whether
phase C complies with the conditions necessary for
second harmonic blocking or not.
•
UHARM_IN_BLOCK
: Signal which indicates whether
the calculated neutral complies with the conditions for
second harmonic blocking or not.
•
UHARM_INS_BLOCK
: Signal which indicates whether
the sensitive neutral complies with the conditions
necessary for second harmonic blocking or not.
The diagram below shows how to wire the second harmonic
blocking signals to the overcurrent units:
Figure 4.15.
Cabling by second harmonic
The blocking input signals of the overcurrent units are the
result of the logic carried out between the “U2HARM_IX_
BLOCK” blocking signal generated by the second harmonic
blocking unit and the “
Blocking mode
” setting of the
corresponding overcurrent unit. In consequence, whenever
blocking conditions exist, the corresponding overcurrent
unit is blocked in the way indicated by the “
Blocking mode
”
setting of the associated unit.
The possible blocking modes are:
•
OFF
: The unit is not blocked even when the conditions
necessary for blocking come about.
•
UNIT
: Blocks the unit, preventing start-up whenever the
conditions necessary for blocking come about.
•
TIMING
: Freezes the time counter value whenever the
conditions necessary for blocking come about.
•
TRIP
: Allows the unit to advance and blocks it before
the trip output, whenever the conditions necessary for
blocking come about.