VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
41
Strap-On Leaving Water Temperature Sensor Wiring
Place
Between Pipe
And Sensing Element. Pipe Should Be
Clean And Smooth To Provide Proper
Thermal Contact With Sensing Element.
Thermal Mastic
Secure Sensor Element And Thermal
Mastic Strip To Pipe With Supplied
Wire Tie. Be Sure To Tighten Wire Tie
Snugly To Ensure Good Thermal
Contact.
Butt Splice Or Wire Nut Wire Leads And Extend
Wire To Controller Terminals. Connect One Wire
Lead To Leaving Water Temperature Terminal (T2)
At The Controller. Secure Other Wire Lead To
Ground Terminal At The Controller. See Note 3.
And Detailed Wiring Diagram Below.
Notes:
1.)Sensor Should Be Mounted At
Location Along Pipe Length
That Best Represents Desired
Temperature Reading.
3.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
2.)Sensing Element Shown
Mounted To Top Of Pipe. The
Sensor Element May Be Located
At Any Location Around Pipe.
Wire Tire
(Supplied)
Sensing Element
(Supplied)
Thermal Mastic Strip
(Supplied)
Leaving Water Pipe
See Note 1 & 2.
Caution:
For Accurate Temperature
Readings It Is Necessary To
Place Insulation Over The
Sensor After Installation.
This Prevents The Ambient
Temperature From Affecting
The Sensor. Insulation
Should Cover The Sensor
And Extend 6” to 12”
Beyond Each End Of The
Sensor.
O 233 Leaving Water
Temperature Sensor
E
Figure 27: OE233 Strap-On Leaving Water Temperature Sensor Installation
Revised 9/18/13